The CT connection test is simple tool for right current transformers' connection analysis. It uses the
first four compensation outputs for detection of individual phase current angles. The only condition
must be fulfilled for the CT test usage : either
three-phase
or
single-phase
compensation
capacitors
are connected to
the first four
control outputs
. If, for example, two-phase capacitors or any chokes
connected to the outputs, the CT test gets fail results !
If inappropriate compensation elements connected to the first four outputs,you can set such
outputs temporary to
the fixed-off
control state; then the instrument will use tor the CT test
the next four outputs that are set as
the control
outputs.
The CT test can be launched manually only. Navigate to the last option of
the Control
group of the
PFC setting and select
the CT Test
. After the command being confirmed, the information screen
appears :
Fig. 4.16 : CT Test Info Message
During following 10 seconds, you can either cancel the start command with the
button or to skip the
message timeout with the
button to start the CT test immediately. Or you can simply let the timeout
to expire and then the CT test starts.
The CT test window shows information about individual phase current inputs' connection. At the
beginning of the test, following message is shown :
L1 L2 L3
CT : - - - - - - - - -
The dashes mean that the test result is not yet ready now.
First of all, the first four of control outputs are disconnected, step by step. Then the instrument waits
until discharge time of the outputs just disconnected expires - such undischarged outputs can be
identified with decreasing shadow filling. During this,
Output 1.1
(for example ) message flashes in the
headline, that means that the instrument waits till output No. 1.1 is ready to use.
Fig. 4.17 : CT Test Window
When the outputs used for the testing are discharged, the instrument starts to switch the outputs step
by step. After each of the step is switched off, the result of reactive and active powers and evaluated
current signal angle of individual phases appears at the bottom of the CT test window. If the
measurement is not successful, dashes appear instead the test results ( this is not unusual that such
results appear, especially if high power load in the network or if the powers of outputs that are used of
testing are low, compared to the network load ).
47
CT Connection Test
(1-p or 3-p capacitors supposed
at the first 4 control outputs)
will be started in
10 secs
Summary of Contents for NOVAR 2600
Page 82: ...NOVAR 2600 Operating Manual NOVAR 2600 T18 Typical Installation 82...
Page 83: ...NOVAR 2600 Operating Manual NOVAR 2600 T7 Typical Installation 83...
Page 87: ...NOVAR 2600 Operating Manual NOVAR 2600 T External Temperature Sensor Connection 87...
Page 88: ...NOVAR 2600 Operating Manual NOVAR 2600 4 RS485 Remote Communication Connection 88...
Page 89: ...NOVAR 2600 Operating Manual 8 Manufactured Models and Marking 89...