NOVAR 2600 Operating Manual
If the CT-ratio is not set (or its value is 5/5 A or 1/1 A), call for the CT-ratio setting appears
before the AOR- process is launched. When this call is ignored and the CT-ratio is not set
properly the power values of outputs recognized during the AOR-process will be incorrect.
As soon as the process is initiated, the information message appears in the main PFC screen :
Fig. 4.14 : AOR Start Message
During following 10 seconds, you can either cancel the start command with the
button or to skip the
message timeout with the
button to start the AOR process immediately. Or you can simply let the
timeout to expire and then the AOR process starts.
First of all, all of control outputs (i.e. excluding the fixed ones and optional alarm/fan/heating ones )
are disconnected, step by step. Actual state of the outputs can be watched on left part of the screen :
•
… disconnected output, fully discharged, unknown (or zero) type
•
… disconnected output, not fully discharged
•
… connected output
Then the instrument waits until discharge time of the outputs just disconnected expires - such
undischarged outputs can be identified with decreasing shadow filling. During this,
Output 1.1
message flashes in the headline, that means that the instrument waits till output No. 1.1 is ready to
use.
Fig. 4.15 : AOR Process Screen
After all of the outputs discharged, the instrument starts to switch the outputs step by step. After each
of the step is switched off, its type and size is displayed for short time. From the example above you
can find :
•
the output No. 2.1 that was just measured was recognized as three-phase capacitor with total
(ΣL) reactive (nominal) power of 19.9 kvars
•
individual phase powers of the capacitor are 6.36/6.53/6.98 kvars
•
the output No. 2.2 is just being tested (switched on)
•
up till now, outputs No. 1.1, 1.2, 1.4, 1.7, 1.8. 1.9 and 2.1 have been recognized as three-
phase capacitors
•
outputs No. 1.3, 1.5 and 2.2 ÷ 2.7 have been recognized as “zero outputs” (with no reactive
power response)
45
Automatic Output
Recognition will be started
in 10 secs
output type
recognized
output 3-p
reactive power
output reactive &
active phase
components
output No.
just being
analyzed
Summary of Contents for NOVAR 2600
Page 82: ...NOVAR 2600 Operating Manual NOVAR 2600 T18 Typical Installation 82...
Page 83: ...NOVAR 2600 Operating Manual NOVAR 2600 T7 Typical Installation 83...
Page 87: ...NOVAR 2600 Operating Manual NOVAR 2600 T External Temperature Sensor Connection 87...
Page 88: ...NOVAR 2600 Operating Manual NOVAR 2600 4 RS485 Remote Communication Connection 88...
Page 89: ...NOVAR 2600 Operating Manual 8 Manufactured Models and Marking 89...