NOVAR 2600 Operating Manual
Tab 4.3 : PFC Alarms
alarm
mark
alarm event
control
quantity /
event
limit
setting
range
activation
(/ deact.)
delay
default setting
I
ndication,
A
ctuation
notes
U<<
voltage loss
U
LN
(1 period)
20% of U
NOM
(fixed)
0.02 sec /
5 sec(fixed)
-
I
+
A
simultaneous
disconnection
U<
undervoltage
U
LN
/
U
LNAVG
20÷100% of U
NOM
1 sec ÷ 20
min
U
LN
/ 70 % / 1 min
U>
overvoltage
U
LN
/
U
LNAVG
100÷200% of
U
NOM
1 sec ÷ 20
min
U
LN
/ 130 % / 1min
I<
undercurrent
I /
I
AVG
0÷25.0 % of In
*)
1 sec ÷ 20
min
I / 0.1 % / 5 sec
I
+
A
fixed sections
not affected
by actuation
I>
overcurrent
I /
I
AVG
100÷140 % of In
*)
1 sec ÷ 20
min
I / 120 % / 1 min indication
only
CHL>
CHL limit exceeded CHL /
CHL
AVG
80÷300 %
1 sec ÷ 20
min
CHL/133 % / 1min
THDU
>
THDU limit
exceeded
THDU /
THDU
AVG
1÷300 %
1 sec ÷ 20
min
THDU /10 % /
1min
THDI>
THDI limit
exceeded
THDI /
THDI
AVG
1÷300 %
1 sec ÷ 20
min
THDI / 20 % / 1min
P><
P limit exceeded /
drop
Pfh /
Pfh
AVG
0÷99 %
1 sec ÷ 20
min
0 % / 5 sec
fixed sections
not affected
by actuation
PF><
PF control failure -
PF control deviation
out of contr. b'width
ΔQfh /
ΔQfh
AVG
-
1 sec ÷ 20
min
ΔQfh
AVG
/ 5 min
I
indication
only
NS>
number of switching
operations
exceeded
number of
switching
operations
1÷9999
thousands
immediatel
y(0 sec)
100
I
indication
only
OE
output error
section
failure
0÷99 % of
reading
3 ÷ 15
consecut.
occurr'nces
20 %; 10
I
+
A
T1><
T2><
temperature
exceeded / drop
Ti
(internal) /
Te
(external)
-40 ÷ +60 °C
1 sec ÷ 20
min
>+45 °C / 1 sec
>+35 °C / 1 sec
EXT
external alarm
active
digital input
state
-
0.02 sec /
5 sec(fixed)
-
simultaneous
disconnection
OoC
out of control
PF control
process not
running
-
1sec ÷
20min
/ imm'tely
15 min
indication
only
RCF
remote control
failure
remote
control
process
state
-
1sec ÷
20min
/ imm'tely
1 min
indication
only
PF>
PF control failure –
overcompensated
PFfh /
PFfh
AVG
cos : 0.00(C/
L) ÷ 1.00
1 sec ÷ 20
min
PFfh / 1.00
/
1 min
indication
only
PF<
PF control failure –
undercompensated
PFfh /
PFfh
AVG
cos :
0.00(C/L) ÷ 1.00
1 sec ÷ 20
min
PFfh / 0.95L
/
1 min
indication
only
Note : *) In ... CT secondary rated current; 5A or 1A according the CT-ratio setup
37
Summary of Contents for NOVAR 2600
Page 82: ...NOVAR 2600 Operating Manual NOVAR 2600 T18 Typical Installation 82...
Page 83: ...NOVAR 2600 Operating Manual NOVAR 2600 T7 Typical Installation 83...
Page 87: ...NOVAR 2600 Operating Manual NOVAR 2600 T External Temperature Sensor Connection 87...
Page 88: ...NOVAR 2600 Operating Manual NOVAR 2600 4 RS485 Remote Communication Connection 88...
Page 89: ...NOVAR 2600 Operating Manual 8 Manufactured Models and Marking 89...