NOVAR 2600 Operating Manual
Actual output cursor position on the example is 1.1 which is given by :
•
the number 1 is inverse, i.e. the first output of an output group is selected
•
actually selected group is marked with the bar below the group icon column, which is No.1
now (the left column)
When you want, for example, to switch the output No. 1.6 navigate with the
button to the
output No. 6. Now, you can switch the output No. 1.6 on by pressing the
button or switch it off
with the
button. Note that all of not fully discharged outputs are blocked against switching on.
As soon as the
button released, the manual output control process is cancelled.
You can use the manual output control not only in the manual state but even during power factor
control state as well, which can be usable for control process checking. For this, press the
button and keep it pressed – after approx. 3 seconds, the pull up menu disappears and the button icon
switches to the
, which means the manual output control gets active. Now you can toggle the
outputs in the same way as in the manual state. But note that the power factor control process is still
running on the background and manual interventions can be corrected back by the simultaneous
control process. For the same reason you cannot change fixed outputs and zero outputs state
because being under control of the control process.
4.2.1.9.2 PFC Setup Direct Access Button
As the NOVAR 2600 controllers are complex instruments, their presetable parameters are for better
orientation hierarchically arranged into several groups that are accessible in standard way via
main
menu
.
But during power factor control systems installation, commissioning and checking it is usually
necessary to check or to modify the parameters affecting power factor control process frequently and
standard access to the parameters may prove cumbersome. Therefore, direct access to the PFC
setup parameters from the main PFC screen was implemented using the
button.
4.3 PFC Setup Parameters
You can get into the
PFC Setting
menu from the main menu via
Settings
→
PFC Setting
, or simply
by pushing the
button.
The PFC Setting
menu appears :
Fig. 4.4 : PFC Setting Menu
The complete PFC setting consists of a series of parameters arranged into three groups :
the PFC
Control
,
the PFC Outputs
and
the PFC Alarms
. Next two options in the menu are
the Control <->
Manual
state toggle and
the PFC Factory Setting
utility.
By selection of any of the first three icons appropriate parameter group list appears. You can browse
throw them using the the ▲and ▼buttons. Some subgroups of parameters are arranged
hierarchically in sublevels – push the
button to entry into a sublevel and the
(escape)
button to return back.
If the instrument is not locked you can edit parameter values. Select desired parameter and push the
button – the parameter edit window appears where you can set the value. Then push the
button
again and the new value is stored. But note that, for now, new values of the parameter group are
restored into a temporary memory only, real parameter values are not yet changed now ! After all
24
Summary of Contents for NOVAR 2600
Page 82: ...NOVAR 2600 Operating Manual NOVAR 2600 T18 Typical Installation 82...
Page 83: ...NOVAR 2600 Operating Manual NOVAR 2600 T7 Typical Installation 83...
Page 87: ...NOVAR 2600 Operating Manual NOVAR 2600 T External Temperature Sensor Connection 87...
Page 88: ...NOVAR 2600 Operating Manual NOVAR 2600 4 RS485 Remote Communication Connection 88...
Page 89: ...NOVAR 2600 Operating Manual 8 Manufactured Models and Marking 89...