48
EVO-S COMPACT
COMPACT AIR HANDLING UNIT
OPERATION AND MAINTENANCE MANUAL
4.7 RR rotary exchanger
In RR sets, heat recovery takes place in a rotary regenera-
tor, with a recovery efficiency of up to 85%. Outlet warm air
flows through the rotor section and heats it up. The rotor
transfers heat from the heated part to the cold air in the in-
take part. For summer conditions it is also possible to recov-
er cold and humidity.
Rotary exchangers can be used in cases where a slight mix-
ing of the exhaust and supply air is possible. The internal
tightness is defined above 97% when the rotor is installed
on the suction side of the fans.
The rotor kit includes a rotary exchanger and a drive mecha-
nism. A sluice is mounted on the rotor’s supporting construc-
tion, which prevents excessive leakage of the exhaust air.
The section housing has an inspection cover allowing ac-
cess to the drive mechanism and the rotor.
The drive mechanism consists of a belt transmission, an
electric motor (OJ-MRHX) and an engine base that automat-
ically regulates the drive belt tension.
The motor is supplied with the OJ-DRHX controller and both
units are connected by a factory-supplied cable.
OJ-DRHX is equipped with advanced software to monitor
the rotation of the rotary exchanger; no additional control
is required for breaking the drive belt (induction sensor or
other solution).
The combination of high-torque stepper motor and Field
Oriented Controls (FOC) technology provides an excep-
tionally innovative solution and increased efficiency. The
automation uses a feedback signal from the engine to make
sure that the engine selects exactly the required amount of
current to achieve the required speed and torque.
The rotor is made up of layers of aluminium foil winded on
the axis of rotation, alternately smooth and corrugated,
forming channels for airflow. To recover the latent heat re-
sulting from the humidity difference, the foil is additionally
covered with a layer of hygroscopic material.
The exchanger should be equipped with an anti-frost sys-
tem, which will protect the device against the effects of ex-
cessive cooling of the exhaust part of the exchanger.
The protection consists of (on delivery of the manufactu-
rer’s automation):
• differential pressure sensor (pressure switch) before
and behind the exchanger on the exhaust air side,
When the preset pressure drop on the pressure switch is re-
ached, as a result of the exchanger defrosting, the controller
sends a signal to the inverter to smoothly reduce the rotor
speed.
NOTE: The rotary exchanger is supplied without a frost
protection system as standard. The type of system is deter-
mined by the ventilation and automation system designer.
A pressure system is recommended. The pressure switch
setting should be 150% of the designed air pressure drop on
the exchanger on the outlet side.
The value of pressure drop is given in the technical data of
the air handling unit.
4.7.1 Rotary exchanger drive
Tab. No 17
Technical data for OJ-DRHX regulators
Unit
DRHX-1055-
MNN5
DRHX-1220-
MNN5
DRHX-1690-
MAN5
Efficiency
Nm
2.0
4.0 / 8.0
14.0
Power data
W
55
220
690
Voltage
%
>90%
>94%
Power data
Voltage
VAC
1 x 230 V AC 50/60 Hz -10%/+10%
Current (at max load)
A
0,6
1,2 / 2,4
4,4
Power (at max. load)
0,69
> 99 (Active
PFC)
Output data
Nominal engine power (shaft)
W
55
110 / 220
690
Rotary speed
rpm
0-250
0-400
Nominal torque
Nm
2.0
4.0 / 8.0
14.0
Increased torque
Nm
2.5
5.0 / 10.0
17.5
Frequency
Hz
0-120
Maximum output voltage
Vrms
3 x 0-150V AC
3 x 0-230VAC
Maximum output current
Arms
2.5
3.5
4.5
Protection
Maximum fuse value
A
10
Engine output
Interphase short-circuit protection
Engine
Protection by limiting current
Surge protection
No
Yes, 400V (PTC)
Overload protection
Protection against current and temperature
overload
EMC
Built-in EMC filter
Environment
Operating temperature
O
C
-40
O
C / +40
O
C
Storage temperature
O
C
-40
O
C / +70
O
C
Dimensions
mm
183 x 143 x 55
185x220x90
Protection
IP
54
Workmanship material
Plastic
Metal
Weight
kg
0,9
2.0
Humidity
% rh
10-95% rh, no condensation
Interface
Modbus protocol
MODBUS RTU RS485
(Baud rate: 9.6, 19.2, 38.4, 57.6, 115.2 Kbaud)
Default: 38.4k baud, 1 stop bit, none parity
Modbus connection
2 x RJ12 i 3 spring clams
Modbus wire
Maximum 100m
Tab. No 18
Technical data for OJ-DRHX motors
MRHX-3P02N-03C5
Unit
Wartość
Torque
Nm
2.0
Power
W
55
Weight
kg
≈ 2.4 kg
Protection
IP
54
Operating temperature
O
C
-40
O
C / +40
O
C
Storage temperature
O
C
-40
O
C / +70
O
C
Dimensions
mm
85 x 85 x 67
Shaft dimension
mm
12
Cable length
m
0,3
Summary of Contents for EVO-S COMPACT
Page 2: ...SERWIS SERVICE 4858 7839950 51 48 510098081 serwis klimor com...
Page 30: ...SERWIS SERVICE 48 587839950 51 48 510098081 seriws klimor com...
Page 58: ...SERWIS SERVICE 48 587839950 51 48 510098081 serwis klimor com...
Page 59: ...EVO S COMPACT KLIMOR...
Page 65: ...63 7 8 9 10 11 50 DN40 11...
Page 67: ...65 b 200x200 16 17 16 17 c 200x200 300x200 18 18 3 2 2 EVO 2000 5100 5610 19 13 M12 M12 M12 19...
Page 68: ...66 EVO S CO CT 2900 a 50 20 b 150 21 c 22 2900 b c...
Page 75: ...73 31 32 30 10 20 1 100 C 2 3 32 4 5 DX 0 03 4 5 2 12 12 4 5 3 DX...
Page 76: ...74 EVO S CO CT CHA 4 5 4 34 4 5 5 35 4 5 6 DX 36 DX MHA...
Page 82: ...80 EVO S CO CT 8 19 1 2 3 DX 4 5 6...
Page 84: ...82 EVO S CO CT c IP54 d e 41 1 1 42 f A IP65...
Page 85: ...83 11...
Page 86: ...SERWIS SERVICE 48 587839950 51 48 510098081 serwis klimor com...
Page 87: ......