42
EVO-S COMPACT
COMPACT AIR HANDLING UNIT
OPERATION AND MAINTENANCE MANUAL
4. FUNCTIONAL UNITS
Depending on the functional requirements resulting from
the air handling process, the units are equipped with the
following batch units:
4.1 MX Mixing and recirculation
All rectangular inlets and outlets in the units are equipped with
flexible connection. They are screwed to the damper or the air
handling unit cover. Size of flexible connection and rectangu-
lar dampers for individual units according to section 2.2.4
Connections are secured for transport by means of metal
strips. The flexible connection is equipped with a yellow-green
grounding wire, which should not be removed, but connected
to the duct system.
4.2 Air filters P, B, MP
Air filters can be supplied in accordance with PN-EN 779 or
PN-EN-ISO 16890. Filter classification is given in the Table 9.
Table 9.
Classification of filters used in EVO units
Filter thick-
ness [mm]
Type of filter
Standard
PN-EN 779
PNEN PN-EN ISO 16890
50
Cassete
G4
Coarse 80%
50
Cassete
M5
ePM10 50%
300
Bag
G4
Coarse 60%
300
Bag
M5
ePM10 50%
500
Bag
F7
ePM2,5 65%
500
Bag
F9
ePM1 70%
48
mini pleat
M5
ePM10 70%
96
mini pleat
F7
ePM1 60%
96
mini pleat
F9
ePM1 80%
In the pre-filtration section PF, cassette filters class G4÷M5,
bag filters class G4 and M5 or minipleat class M5 are instal-
led.
In the secondary filtering section SF, bag filters class F7 and
F9, minipleat class F7 and F9 filters
The dimensions of the filters used are specified in the KT
certificate.
The filters must be replaced when the permitted pressure
drop at the filter is exceeded (Table 10) or according to a vi-
sual decision in the automation system.
The unit must be switched off during filter renewal.
The class of new filters has to correspond to the class of the
used filters.
During filter renewal also the filtration section has to be cle-
aned.
Table 10.
Acceptable filter pressure drop
Filter class
Acceptable filter pressure drop
(according to PN-EN13053:2011)
G1÷G4
150 Pa
M5÷F7
200 Pa
F8÷F9
300 Pa
4.2.1 Cassete Filter G4 and M5
G4/M5 cassette filters (panel filters) are fabric filters in metal
casing; they are designed for preliminary air treatment.
Cassete filters are 50mm deep. They are mounted in straight
SR type guides.
Self-adhesive seals for sealing are mounted on the walls of
the air handling unit housing at the point of filter adhesion
and between cassettes, if there are more filters.
Cassette filters are not to be regenerated and must be repla-
ced with new ones.
The dimensions of the filters used are specified in the KT
certificate.
Table 11.
Dimensions and quantities of metal and panel cassette filters
Size
EVO
W
H
pcs
Size
EVO
W
H
pcs
[mm]
-
[mm]
-
5100
605
350
1
0600
1205
650
1
3200
855
350
1
0700
700
650
2
0300
855
450
1
5800
700
800
2
0400
1105
450
1
0010
800
800
2
2500
1205
550
1
5310
850
1050
2
5610
950
1150
2
4.2.2 Minipleat filters
M5 minipleat filters
M5 class minipleat filters are filters made of non-woven fa-
bric formed into filter packets in galvanized sheet casing;
they are designed for preliminary air treatment.
M5 minipleat filters are 48mm deep. They are mounted in
straight SR type guides.
Self-adhesive seals for sealing are mounted on the walls of
the air handling unit housing at the point of filter adhesion
and between cassettes, if there are more filters.
M5 minipleat filters are not to be regenerated and must be
replaced with new ones.
The dimensions of the filters used are specified in the KT
certificate.
Table 12.
Dimensions and quantities of M5 minipleat filters
Size
EVO
W
H
pcs
Size
EVO
W
H
pcs
[mm]
-
[mm]
-
5100
600
350
1
0600
599
650
2
3200
424
350
2
0700
465
650
3
0300
424
450
2
5800
465
800
3
0400
549
450
2
0010
532
800
3
2500
599
550
2
5310
565
1050
3
5610
473
1150
4
Summary of Contents for EVO-S COMPACT
Page 2: ...SERWIS SERVICE 4858 7839950 51 48 510098081 serwis klimor com...
Page 30: ...SERWIS SERVICE 48 587839950 51 48 510098081 seriws klimor com...
Page 58: ...SERWIS SERVICE 48 587839950 51 48 510098081 serwis klimor com...
Page 59: ...EVO S COMPACT KLIMOR...
Page 65: ...63 7 8 9 10 11 50 DN40 11...
Page 67: ...65 b 200x200 16 17 16 17 c 200x200 300x200 18 18 3 2 2 EVO 2000 5100 5610 19 13 M12 M12 M12 19...
Page 68: ...66 EVO S CO CT 2900 a 50 20 b 150 21 c 22 2900 b c...
Page 75: ...73 31 32 30 10 20 1 100 C 2 3 32 4 5 DX 0 03 4 5 2 12 12 4 5 3 DX...
Page 76: ...74 EVO S CO CT CHA 4 5 4 34 4 5 5 35 4 5 6 DX 36 DX MHA...
Page 82: ...80 EVO S CO CT 8 19 1 2 3 DX 4 5 6...
Page 84: ...82 EVO S CO CT c IP54 d e 41 1 1 42 f A IP65...
Page 85: ...83 11...
Page 86: ...SERWIS SERVICE 48 587839950 51 48 510098081 serwis klimor com...
Page 87: ......