Approved for Power Vent PVH58 / PVH58FM
- This appliance is approved for use with a Kingsman PVH58 Horizontal Power Vent -
A Horizontal Power Vent Termination is intended for use where standard venting configurations are
not possible.
NOTE:
MODELS EQUIPPPED WITH MILLIVOLT/ STANDING PILOT IGNITION: Downward vertical vent runs are
NOT
permitted.
NOTE:
MODELS EQUIPPPED WITH INTERMITTENT PILOT IGNITION (Proflame 1 or Proflame 2):
Downward vertical vent runs are permitted, however, Cold Climate Switch (Standing Pilot Mode) must
NOT
be used.
Seven 90° elbows are possible if the total horizontal is not more than 25ft and the vertical does not exceed 15ft.
Refer to Power Vent Manual for proper installation and use.
Maximum / Minimum Vent Lengths:
Maximum
Vent Length is 125 ft plus six 90° elbows with Air Intake Shutter fully closed. Termination must not be
below unit.
This power vent can be installed up to
8ft
below the installed fireplace on runs less than 100ft and not more than
four 90° elbows.
Minimum
Vent Length is 1 FT vertical x 3 FT horizontal x 3 FT vertical x 3 FT horizontal (See PVH58 manual).
79