background image

 

KFP-CE4 Series 

Installation Manual 

P/N 501-415503-1-31 

• REV 

03.10 

• ISS 08NOV13

 

Summary of Contents for KFP-CE4 Series

Page 1: ...KFP CE4 Series Installation Manual P N 501 415503 1 31 REV 03 10 ISS 08NOV13 ...

Page 2: ... EC WEEE directive Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union For proper recycling return this product to your local supplier upon the purchase of equivalent new equipment or dispose of it at designated collection points For more information see www recyclethis info 2006 66 EC battery directive This product contains a battery that canno...

Page 3: ...dvanced configuration 36 Expansion board configuration 46 Fire network and repeaters configuration 48 Commissioning 54 Chapter 4 Maintenance 59 System maintenance 60 Battery maintenance 60 Chapter 5 Technical specifications 63 Zone specifications 64 Input and output specifications 65 Power supply specifications 66 Mechanical and environmental specifications 67 Fire network specifications 68 Cabine...

Page 4: ...oss of life Caution Caution messages advise you of possible equipment damage They tell you which actions to take or to avoid in order to prevent the damage Note Note messages advise you of the possible loss of time or effort They describe how to avoid the loss Notes are also used to point out important information that you should read Limitation of liability To the maximum extent permitted by appl...

Page 5: ... this manual applicable codes and the instructions of the authority having jurisdiction is mandatory While every precaution has been taken during the preparation of this manual to ensure the accuracy of its contents UTCFS assumes no responsibility for errors or omissions ...

Page 6: ...iv KFP CE4 Series Installation Manual ...

Page 7: ...s Installation Manual 1 Chapter 1 Introduction Summary This chapter provides an introduction to your control panel and the available operating modes Content Product range 2 Product compatibility 2 Operating modes 2 ...

Page 8: ...upplied compatibility list Compatibility with products that are not listed in that document cannot be guaranteed For further details contact your local supplier Operating modes Supported operating modes are shown in the table below The default operating mode is NEN 2575 with four evacuation areas Table 1 Operating modes Operating mode EN 54 13 option 1 Region NEN 2575 4E default Available 2 Europe...

Page 9: ...P CE4 Series Installation Manual 3 When the panel is configured for EN 54 13 zone supervision the corresponding insert shows a Fault Output Fault Disabled LED for use in the fault warning output supervision required by EN 54 13 ...

Page 10: ...Chapter 1 Introduction 4 KFP CE4 Series Installation Manual ...

Page 11: ...ns Content Cabinet layout 6 Cabinet installation 7 Preparing the cabinet 7 Where to install the cabinet 7 Fixing the cabinet to the wall 7 Menu inserts 9 Connections 10 Recommended cables 10 Overview of fire and evacuation system connections 10 Connecting zones and zone devices 13 Connecting inputs 14 Connecting supervised outputs 16 Connecting the mains power supply 18 Selecting 115 or 230 VAC op...

Page 12: ...m connectors 3 Cable knockouts 4 Mounting screw knockouts 5 Network board connector on the back of the PCB 6 Battery area 7 Power supply unit 8 Key connector 9 Alarm counter connector 10 Fuse terminal block 11 Power supply connector 12 Battery connector 13 Expansion board connector 14 Cable holder Note Only selected regional models have the key and alarm counter connectors ...

Page 13: ...al specifications on page 63 for more information on the operating temperature and relative humidity specifications Allow for enough floor and wall space so the panel can be installed and serviced without any obstructions The cabinet should be mounted so that the user interface is at eye level Note that the control panel must be assembled and installed according to the ordinances and codes that ar...

Page 14: ... control panel cabinet to the wall 1 Mark drill points on the wall using the cabinet as a template 2 Drill all required holes and insert a 6 mm wall plug into each 3 Insert screw 1 half way and hang the cabinet onto this screw 4 Insert screws 2 and tighten 5 Insert screws 3 and tighten 6 Tighten screw 1 ...

Page 15: ...includes a label for the Fault Output Fault Disabled LED Use the printed insert identified as NEN2575 EN 54 13 To apply the menu inserts 1 Add the detection zone names and evacuation area names to the top insert segment Detection zone names go in the left column Evacuation area names go in the right column above the preprinted LED label text 2 Detach the four insert segments from the sheet 3 Remov...

Page 16: ...12 to 26 AWG 3 31 to 0 13 mm Twisted pair max 40 Ω 500 nF 2 km Zone circuit cable automatic or manual zones 12 to 26 AWG 3 31 to 0 13 mm Twisted pair max 55 Ω 500 nF 2 km Fire network cable Twisted pair Cat 5 12 to 26 AWG 3 31 to 0 13 mm 1 2 km Note Other types of cable may be used subject to site specific EMI conditions and installation testing Use 20 mm cable glands to ensure clean and secure co...

Page 17: ...Chapter 2 Installation KFP CE4 Series Installation Manual 11 Figure 4 Standard system connections no EN 54 13 requirement Figure 5 Standard system connections for EN 54 13 compliance ...

Page 18: ...onnections 1 A diode must be connected on the detector base Consult your detector installation manual for more details Figure 7 Intrinsically safe system connections 1 Galvanic barrier for intrinsically safe conventional detectors 2 Galvanic barrier for intrinsically safe fire notification devices ...

Page 19: ...th a multimeter Note The default zone detection settings for each operating mode can be found in Appendix A Configuration presets on page 71 To change the zone detection setting see Advanced configuration on page 36 Terminating zones Zone termination is required at all times whether the zone is used or not The type of termination depends on the installation as shown in Table 4 below Table 4 Zone t...

Page 20: ...5 MCP resistances Zone type Manual call point resistance 1 Standard active end of line EN 54 13 Intrinsically safe Mixed 100 Ω Not supported Not supported Manual 100 to 680 Ω 100 to 470 Ω 250 to 560 Ω 1 Resistance must be rated at 1 W minimum Note The default zone detection settings for each operating mode can be found in Appendix A Configuration presets on page 71 To change the zone detection set...

Page 21: ...N A Extended fire routing delay 9 kΩ 9 kΩ Fire routing inhibit delay 9 kΩ 9 kΩ Class change 9 kΩ 9 kΩ Delays off 9 kΩ 9 kΩ Connecting supervised inputs Connect supervised input switches to INPUT1 and INPUT2 as shown in Figure 8 below Figure 8 Connecting supervised inputs Nominal resistance values including any cable resistance are shown in Table 8 below Table 8 Nominal resistance values for superv...

Page 22: ... Output classes and EN 54 13 supervision Output class EN 54 13 supervision Description Class B default Disabled For installations not requiring EN 54 13 compliance Class A Enabled For installations requiring EN 54 13 compliance For more information see EN 54 13 supervision mode on page 32 Output functionality The function of each output is defined by the panel operating mode and output class confi...

Page 23: ...le 12 below Table 12 Termination required for output classes Output class Output termination Class B default All outputs require a 15 kΩ end of line resistor for termination If an output is not used the end of line resistor must be installed across the unused output terminals see Figure 4 on page 11 Class A EN 54 13 All outputs require a 4 7 kΩ 1 4W 1 end of line resistor for termination If an out...

Page 24: ...al equipment Note This feature is only available in EN 54 13 mode with a 2010 1 SB supervised expansion board configured to preset 35 See Expansion board presets on page 74 Connect the external equipment to the OUT3 output on the 2010 1 SB supervised board The wiring must be returned back to the control panel to the 2010 FS EOL user supervisory board connected to INPUT2 as shown below Figure 9 Con...

Page 25: ...nt Figure 10 Connecting the mains power supply 1 Mains fuse 2 Live 3 Earth 4 Neutral For fuse specifications see Chapter 5 Technical specifications on page 63 Selecting 115 or 230 VAC operation WARNING Electrocution hazard To avoid personal injury or death from electrocution remove all sources of power and allow stored energy to discharge before installing or removing equipment Power switching for...

Page 26: ...ies to the BATT connector on the control panel PCB as shown below Polarity must be observed Note If the control panel indicates a Supply Fault then the batteries may need to be replaced See Battery maintenance on page 60 Figure 12 Connecting the batteries Caution Risk of equipment damage No other equipment may be connected to the BATT connector Powering auxiliary equipment 24 VDC auxiliary output ...

Page 27: ...lay circuit is 2 A at 30 VDC Connecting expansion boards Caution Risk of equipment damage Always disconnect the control panel from the mains power supply before installing an expansion board See your expansion board installation sheet for detailed installation information Connecting a fire network Note See the 2010 1 NB Network Board Installation Sheet for detailed installation and connection info...

Page 28: ...ion Note To be compliant with EU regulations use this network configuration only in cases where the detection zones and mandatory EN 54 2 output functions sounder and fire routing outputs are not remote between panels Bus network configuration is not normally recommended as it does not provide for redundancy in the transmission path For bus configuration Class B connect control panels as shown bel...

Page 29: ...tion overview 27 Configuration controls 27 Common configuration tasks 29 Basic configuration 30 The basic configuration menu 30 Basic default configuration 31 EN 54 13 supervision mode 32 Panel mode 33 Fire routing delay 34 Extended fire routing delay 34 Adding expansion boards 35 Adding a fire network board 35 Advanced configuration 36 The advanced configuration menu 36 Sounder operation during a...

Page 30: ... Expansion board configuration 46 Adding an expansion board 46 Expansion board configuration 46 Fire network and repeaters configuration 48 Basic configuration options 48 Advanced configuration options 50 Commissioning 54 Before commissioning the control panel 54 Commissioning the control panel 55 Functional tests 56 Response times 56 ...

Page 31: ...a buttons and LEDs 3 Supply LED 4 General Fault LED 5 General Fire Alarm LEDs 6 All Sounders Stop button 7 Confirm button 8 Network Fault LED 9 Reserved for special use 10 Expansion I O Fault Disabled LED 11 General Disable button and LED 12 General Test button and LED 13 Configuration controls 14 Reset button and LED 15 Panel Silence button and LED 16 All Sounders Start button and LED 17 System F...

Page 32: ...lows basic operating tasks such as responding to fire alarms or fault warnings at the control panel or manually activating evacuation areas No password is required Operator user The operator user level allows additional operating tasks that command the system or perform maintenance functions It is reserved for authorized users who have been trained to operate the control panel Consult the operatio...

Page 33: ...en the seven segment display defaults to the custom display operating mode See Panel mode on page 33 for details Configuration overview To facilitate rapid configuration of the most common tasks configuration is divided into basic and advanced levels For basic configuration options see Basic configuration on page 30 For advanced configuration options see Advanced configuration on page 36 Note The ...

Page 34: ...er Confirms a menu selection or a value selection entry 1 1 Panels configured as repeaters in a fire network normally display the status of several panels Pressing this button for 3 seconds provides a temporary display of local panel status The seven segment display The seven segment display is only visible when the control panel cover is removed see Figure 1 on page 6 Figure 18 The seven segment ...

Page 35: ...2 Press Enter When a configuration menu has been selected the Value LED on the seven segment display is steady To select a value 1 Select the required value using the value selection buttons 2 and 4 2 Press Enter To exit configuration mode and save your changes 1 Press Panel Silence 2 Press Enter or 1 Set the display as shown below and then press Enter The Panel Silence LED flashes to confirm that...

Page 36: ...y as shown below and then press Enter To restore the factory configuration 1 Set the display as shown below and then press Enter Basic configuration The default password for basic configuration is 3333 After entering the password the first displayed menu will be Basic default configuration indicating basic installer user level For more information see User level passwords and indications on page 2...

Page 37: ...ee Expansion board configuration on page 46 2 Additional menu options are available if the panel is configured for connection to a fire network i e the fire network identifier is not 00 This requires an optional fire network board See the topics Connecting a fire network on page 18 and Fire network and repeaters configuration on page 46 Basic default configuration Use this menu to select common op...

Page 38: ...e second digit If a custom configuration has been applied via the advanced configuration menu then the second digit is a zero as shown below Display Configuration 41 NEN 2575 four evacuation areas preset configuration 43 NEN 2575 two evacuation areas preset configuration 45 NEN 2575 one evacuation area preset configuration 40 NEN 2575 custom configuration EN 54 13 supervision mode Use this menu to...

Page 39: ...n press Enter Display indications for each operating mode are shown below Display Operating mode NEN 2575 four evacuation areas NEN 2575 two evacuation areas NEN 2575 one evacuation area Custom See Appendix A Configuration presets on page 71 for presets and default settings for each operating mode Custom operating mode A custom operating mode will be indicated if any of the following zone configur...

Page 40: ...re Routing Delay button A steady Fire Routing Delay LED indicates that the delay is enabled Fire routing delay operation The delay applies to the activation of fire routing if configured only if all of the following are true The delay is enabled The initiating device detector or manual call point is installed in an automatic zone or the initiating device is a detector installed in a mixed zone The...

Page 41: ...it delay input activated and no input using the delays off function activated If the conditions exist to apply the delay fire routing and extended fire routing delays elapse concurrently when a fire alarm event is reported After an alarm condition the fire routing delay is the active delay to activate fire routing The extended fire routing delay becomes the active delay to activate fire routing wh...

Page 42: ...n for each option is included in the related topic Note All configurable options included in Basic configuration on page 30 are also available from the advanced configuration menu Table 20 The advanced configuration menu Display Menu Values Advanced default configuration Configuration presets as defined in Basic default configuration on page 31 EN 54 13 supervision ON OFF Panel mode NEN 2575 4E NE...

Page 43: ...e Zone delay ON OFF Zone type Mixed Automatic Manual Input configuration Remote reset Delays off Fire routing extended delay Fire routing inhibit delay Class change Fault warning output open supervision Fire routing acknowledgement type 1 Fire routing acknowledgement type 2 User level 2 password 0 to 4444 User level 3 basic password 0 to 4444 User level 3 advanced password 0 to 4444 Control panel ...

Page 44: ...under operation during a zone test configuration menu is active 2 Select a value using the value selection buttons 2 and 4 3 Press Enter 4 Save your changes The available settings for this feature are shown below Display Description The internal buzzer and sounders sound for 5 seconds when an alarm is activated in a zone test The internal buzzer and sounders do not sound when an alarm is activated...

Page 45: ...in the same zone sounders will always re sound if the first alarm is reported by a detector and the new alarm is reported by a manual call point Zone configuration Use this menu to configure zone settings for each zone in your fire alarm and evacuation system The default setting for each operating mode is included in Appendix A Configuration presets on page 71 To configure the zone 1 Set the displ...

Page 46: ... any output activation fire routing and expansion board outputs will consider delay before activation The default setting for all zones is ON For a stand alone control panel you specify the zone using the zone number When the control panel is in a fire network unique zone numbers are created by defining a unique starting number for the first zone in each panel For example if the first zone is numb...

Page 47: ...are not applied Outputs activate immediately when the alarm is reported from this zone Zone type Use this menu to configure the zone type for each zone in your fire alarm and evacuation system The default setting for each operating mode is included in Appendix A Configuration presets on page 71 To configure the zone type 1 Set the display as shown below and then press Enter 2 Select the zone for e...

Page 48: ...ed or an intrinsically safe zone is configured Input configuration Use this menu to configure the functionality of INPUT1 and INPUT2 The default setting for each input is included in Appendix A Configuration presets on page 71 To configure an input 1 Set the display as shown below and then press Enter 2 Select the input for example INPUT1 and then press Enter 3 Select a value using the value selec...

Page 49: ...40 seconds 1 2 An active input indicates acknowledge after fire routing is active An active input in other condition generates a fire routing fault 1 Can be configured for only one input per control panel 2 Supervision for wiring open and short conditions is available A 15 kΩ end of line is required Changing user level passwords Use the corresponding menu option shown below to change the default u...

Page 50: ...et setting on or off The default setting is OFF To configure the 24 V reset 1 Set the display as shown below and then press Enter 2 Select a value using the value selection buttons 2 and 4 3 Press Enter 4 Save your changes The available settings for this feature are shown below Display Description Resetting the control panel resets the AUX 24V output Resetting the control panel does not reset the ...

Page 51: ... control panel Display the software version or serial number for expansion board A Display the software version or serial number for expansion board B Display the software version or serial number for expansion board C Display the software version or serial number for expansion board D Display the software version or serial number for the network board To check the software version 1 Set the displ...

Page 52: ...ree expansion boards can be installed when a fire network board is installed To add an expansion board 1 Set the display as shown below and then press Enter The Expansion I O Fault Disabled LED flashes fast to indicate that the module configuration menu is active 2 Select a value using the value selection buttons 2 and 4 3 Press Enter 4 Save your changes Expansion board configuration Expansion boa...

Page 53: ...00 to 10 minutes 1 Available values depend on the type of expansion board installed and the supervision selected See Appendix A Configuration presets on page 71 Expansion board function Use this menu to configure the expansion board function The default value depends on panel configuration For most configurations the default value is 01 For evacuation panels configured for EN 54 13 the default is ...

Page 54: ...onfiguration This section describes how to configure a fire network of conventional control panels in order to Connect repeaters any conventional control panel can be configured to operate as a repeater Create a fire network of conventional control panels when you need additional conventional zones in your system Create a network including compatible addressable control panels to add more features...

Page 55: ... custom pattern of node numbers the displayed value for nn is Cu 2 Depending on the advanced setting Firenet repeater type nr this setting configures the initial zone repeated or the initial panel repeated A basic fire network is either a panel and a repeater or an eight zone virtual panel composed of two four zone panels To configure a basic fire network 1 Activate networking by selecting the nod...

Page 56: ...anel two the second four zone panel you would change the initial zone number from 1 to 5 Panel one would have zones 1 2 3 and 4 Panel two would have zones 5 6 7 and 8 Note that this setting can be used to configure control panels to repeat the status of control panels in the fire network with the zone LEDs Consult fire network advanced configuration settings for further details Basic fire network ...

Page 57: ...firenet repeater type nr Pn 01 to 32 Default 01 Firenet global controls On OFF Default On Firenet loop class A B Default B Firenet process remote zones On OFF Default On Firenet repeater type 2n Zones Repeater Pn Panels Repeater Default 2n Firenet map Submenu 1 32 Values On OFF Default ON for nodes 1 and 2 OFF for the rest Firenet repeater map Submenu 1 32 Values On OFF Default ON for nodes 1 and ...

Page 58: ...M active for nodes 1 and 2 Panel ID 20 with nM active for nodes 20 and 32 Panel ID 32 with nM active for nodes 20 and 32 Panels 1 and 2 will see each other in one sub network and panels 20 and 32 will be each other in a different sub network Only a firenet wiring open loop fault for class A networks will be shared between the two sub networks Repeater map rM configuration Any control panel in the ...

Page 59: ...ders fire routing and fire protection Examples If we disable zone 1 in control panel 1 and control panel 1 repeats control panel 2 the zone 1 in control panel 2 will also be disabled shared zone completely disabled If we disable zone 1 in control panel 1 but control panel 2 is not repeated zone 1 in panel 2 will not be disabled This allows disabling only part of the shared zone Selecting the loop ...

Page 60: ...utility software if you require this type of advanced configuration If the control panel is configured for remote output control it will no longer activate outputs based on its own logic and will only activate outputs with commands coming from the fire network This mode of operation is fail safe i e if the control panel detects a fire network fault the outputs will activate with the local logic or...

Page 61: ...andby is indicated as follows The Supply LED is steady The Fire Routing Delay LED is steady if a delay has been enabled If any other indicators are on check your installation thoroughly before proceeding Fault startup In accordance with EN 54 2 the control panel has a special startup sequence used after an internal fault has been detected by the control panel This is indicated as follows The Gener...

Page 62: ...s and fire routing where applicable once the delay time has elapsed Using a multimeter verify that the fault relay is activated when a fault is reported and that the alarm relay is activated when an alarm is reported Activate all sounders by pressing the All Sounders Start button and the Confirm button to test evacuation alarm reporting Response times Response times for standard events are as foll...

Page 63: ...anual 57 Event Response time No batteries found fault Less than 3 minutes Mains fault Less than 3 minutes Out of service fault Less than 100 seconds Fuse protection fault Less than 3 minutes System fault Less than 100 seconds Battery high resistance fault Less than 4 hours ...

Page 64: ...Chapter 3 Configuration and commissioning 58 KFP CE4 Series Installation Manual ...

Page 65: ...ntenance Summary This chapter includes information on fire alarm and evacuation system maintenance and battery maintenance Content System maintenance 60 Quarterly maintenance 60 Annual maintenance 60 Cleaning the control panel 60 Battery maintenance 60 ...

Page 66: ...ces and verify that the control panel responds to all fault and alarm events All electrical connections must be visually inspected to make sure that they are securely fastened that they have not been damaged and that they are appropriately protected Cleaning the control panel Keep the outside and inside of the control panel clean Carry out periodic cleaning using a damp cloth for the outside Do no...

Page 67: ...ion and all connections are correct then the batteries should be replaced immediately Replacing batteries Batteries must be replaced periodically as recommended by the battery manufacturer The useful life of the battery is approximately four years Avoid the total discharge of the batteries Always use the recommended replacement batteries To replace the batteries 1 Disconnect and remove the existin...

Page 68: ...Chapter 4 Maintenance 62 KFP CE4 Series Installation Manual ...

Page 69: ...r includes technical specifications for your fire alarm and evacuation control panel Content Zone specifications 64 Input and output specifications 65 Power supply specifications 66 Mechanical and environmental specifications 67 Fire network specifications 68 Cabinet drawings and dimensions 69 ...

Page 70: ...s are not EN 54 13 compliant 2 Or as defined by local standards 3 Provided that the detectors meet the required zone specifications given here 4 Figures based on EN 54 2 The maximum number of devices may differ for other standards Table 26 Mixed zone specifications 1 Max resistance per zone circuit 40 Ω Max capacitance per zone circuit 500 nF Nominal impedance Detector Manual call point 160 Ω to 6...

Page 71: ...23 5 V 11 kΩ 1 81 mA 21 3 V High impedance fault N A 16 9 to 17 2 V N A 1 Values are referenced to the IS zone input terminals Input and output specifications Table 28 Unsupervised inputs Cable resistance Activation input value Deactivation input value 9k Ω 10 9k Ω 10 Input type Unsupervised activated with a passive impedance usually a relay contact Sourced current 1 mA max for activation with sho...

Page 72: ...Voltage in alarm For open and short circuit 250 mA max 11 5 VDC max 8 4 VDC max 28 VDC max Alarm relay output Number of potential free outputs Commutation current 1 2 A at 30 VDC max Fault relay output Number of potential free outputs Commutation current Default state 1 2 A at 30 VDC max Energized fail to safe Auxiliary 24 VDC output Voltage Current 24 VDC nominal 28 VDC max 21 VDC min 250 mA max ...

Page 73: ...urrent consumption specifications EN 54 4 Min current consumption Imin 1 0 069 A Max current consumption in standby Imax a 0 39 A Max current consumption in alarm Imax b 2 78 A 1 No faults no battery charging with standard resistive EOL Mechanical and environmental specifications Table 35 Mechanical specifications Cabinet dimensions no cover 421 100 447 mm Weight without batteries 3 9 kg Number of...

Page 74: ... drawings and dimensions see Cabinet drawings and dimensions on page 69 Fire network specifications Table 37 Fire network specifications Maximum distance between control panels 1 2 km Maximum capacity 32 nodes and 64 zones Communication protocol Proprietary peer to peer protocol based on RS 485 ...

Page 75: ...Chapter 5 Technical specifications KFP CE4 Series Installation Manual 69 Cabinet drawings and dimensions Figure 20 Cabinet with cover ...

Page 76: ...Chapter 5 Technical specifications 70 KFP CE4 Series Installation Manual Figure 21 Cabinet without cover ...

Page 77: ...y This appendix includes detailed information on operating mode and expansion board configuration presets Content Operating mode presets 72 NEN 2575 4E presets 72 NEN 2575 2E presets 73 NEN 2575 1E presets 73 Additional configuration characteristics 74 Expansion board presets 74 ...

Page 78: ...activated by a fire alarm in zone 1 Sounder circuit activated by a fire alarm in zone 1 OUT2 Sounder circuit activated by a fire alarm in zone 2 OUT3 Sounder circuit activated by a fire alarm in zone 3 Sounder circuit activated by a fire alarm in zone 2 OUT4 Sounder circuit activated by a fire alarm in zone 4 OUT5 Fire routing activated by a automatic fire alarm device Fire routing activated by au...

Page 79: ...uit activated by a fire alarm in zone 1 or 2 Sounder circuit activated by a fire alarm in zone 1 or 2 OUT2 Sounder circuit activated by a fire alarm in zone 1 or 2 OUT3 Sounder circuit activated by a fire alarm in zone 3 or 4 Sounder circuit activated by a fire alarm in zone 3 or 4 OUT5 Fire routing activated by a automatic fire alarm device Fire routing activated by automatic or manual fire alarm...

Page 80: ...4 OUT5 Fire routing activated by a automatic fire alarm device Fire routing activated by automatic or manual fire alarm device OUT6 Fire routing activated by a manual fire alarm device Additional configuration characteristics Table 44 Additional configuration characteristics for all presets Default fire routing delay 01 Default extended fire routing delay 03 Default zone delay 0n Start Restart sou...

Page 81: ...one Output Delay 01 1 1 Yes 2 2 Yes 3 3 Yes 4 4 Yes 05 1 1 Yes 2 Yes 2 3 Yes 4 Yes 06 3 1 Yes 2 Yes 4 3 Yes 4 Yes 13 1 or 2 1 Yes 3 or 4 2 Yes 5 or 6 3 Yes 7 or 8 4 Yes 15 1 and 2 1 Yes 3 and 4 2 Yes 5 and 6 3 Yes 7 and 8 4 Yes 17 1 2 3 or 4 1 Yes 2 Yes 5 6 7 or 8 3 Yes 4 Yes 18 1 and 2 1 Yes 2 Yes 3 and 4 3 Yes 4 Yes 20 1 or 2 1 Yes 2 Yes 3 or 4 3 Yes 4 Yes ...

Page 82: ... 26 Alarm 1 to 2 No Fault 3 to 4 No 27 Alarm 1 No Fault 2 No Buzzer on 3 No Reset 4 No 29 Fault 1 1 to 4 No 30 Alarm 1 to 2 No Fault 1 3 to 4 No 31 Alarm 1 No Fault 1 2 No Buzzer on 3 No Reset on 4 No 33 Buzzer on 1 No 2 No Reset on 3 No 4 No 33 Buzzer on 1 No 2 No Reset on 3 No 4 No 34 2 Fire Routing Auto 1 No 2 No Fire routing Manual 3 No 4 No 35 2 Fire routing 1 No 2 No Fault warning output 3 3...

Page 83: ...t configuration 4 Configuration 36 is only possible when the Network Remote Output Control option nO is set and it is then configured by default RB SBx is the expansion board x For evacuation panels x can be 1 2 3 or 4 Table 47 Expansion board sounder circuit configuration with EN 54 13 supervision disabled 1 Display Events Output Delay 90 Sounders evacuation output 1 1 No 2 No Sounders evacuation...

Page 84: ...n enabled Display Zone Outputs Delay 05 1 1 and 2 Yes 2 3 and 4 Yes 06 3 1 and 2 Yes 4 3 and 4 Yes 17 1 2 3 or 4 1 and 2 Yes 5 6 7 or 8 3 and 4 Yes 18 1 and 2 1 and 2 Yes 3 and 4 3 and 4 Yes 20 1 or 2 1 and 2 Yes 3 or 4 3 and 4 Yes Table 49 Expansion board event configuration with EN 54 13 supervision enabled Display Event Outputs Delay 24 Alarm 1 and 2 No 3 and 4 No 25 Fault 1 and 2 No 3 and 4 No...

Page 85: ...figuration 4 Configuration 36 is only possible when the Network Remote Output Control option nO is set and it is then configured by default RB SBx is the expansion board x For evacuation panels x can be 1 2 3 or 4 5 Not compliant to EN 54 13 Table 50 Expansion board sounder circuit configuration with EN 54 13 supervision enabled 1 Display Events Output Delay 90 Sounders evacuation output 1 1 and 2...

Page 86: ...Appendix A Configuration presets 80 KFP CE4 Series Installation Manual ...

Page 87: ...KFP CE4 Series Installation Manual 81 Appendix B Product compliance Summary This appendix contains regulatory information that applies to your control panel Content European standards 82 ...

Page 88: ...2010 1 SB expansion board do not support the optional requirement of EN 54 2 clause 7 8 and should not to be used for fire alarm devices 2 Applies only to models with the suffix NL 3 NEN 2575 with EN 54 13 supervision operating mode only European standards for electrical safety and electromagnetic compatibility These control panels have been designed in accordance with the following European stand...

Page 89: ...o the product Declaration of Performance DoP Certification Certification body 0832 Manufacturer UTC CCS Manufacturing Polska Sp Z o o Ul Kolejowa 24 39 100 Ropczyce Poland Authorized EU manufacturing representative UTC Fire Security B V Kelvinstraat 7 6003 DH Weert The Netherlands Year of first CE marking 09 Declaration of Performance number 360 3100 1699 Product identification See model number on...

Page 90: ...Appendix B Product compliance 84 KFP CE4 Series Installation Manual ...

Page 91: ...onnecting fire routing equipment to supervised outputs 17 connecting inputs 14 connecting manual call points 14 connecting sounders or other notification devices to supervised outputs 17 connecting supervised inputs 15 connecting supervised outputs 16 connecting the batteries 20 connecting the fault warning output to external equipment 18 connecting the mains power supply 18 connecting unsupervise...

Page 92: ...eplacing batteries 61 response times 56 ring configuration 21 S select remote output control 54 selecting 115 or 230 VAC operation 19 selecting control panel commands 53 selecting processing for remote zones in alarm 53 selecting the loop class 53 seven segment display 28 software compatibility ii software configuration and serial number information 44 sounder operation during a zone test 38 sound...

Reviews: