Charging current
Factory settings of 0.15C10: The user can set it for 0.07-0.3
Settings
C10.
Automatic conversion between even charging and floating
charging; Automatic temperature compensation of the
Intelligent battery
battery pack (If the system is not connected with the
management
detection line for the battery temperature, the
temperature compensation is based on the ambient
temperature)
Depth of discharge
setting for off-peak
330Vdc-378Vdc (The user can set it)
discharging
Server / bypass
0ms
Conversion
conversion time
time
Bypass/Server
0ms
conversion time
Remote control input
Battery self-check, Server ON/OFF, fault clear, emergency
stop
Communication
Computer
RS232, RS485 and SNMP(Option)
monitoring port
interface
Dry contact output
Bypass input fault, rectifier input fault, system fault, system
12Vdc/250Vac 1A
alarm, battery low voltage, output overload, fan fault and
max
generator ON/OFF.
Operating
0~40
℃
temperature
Environment
Maximum relative
90% (Non-condensing)
humidity
Maximum altitude
Rated power per 100m (1% reduced by rising 100m)
Maximum 4000m
Cooling
Forced ventilation (fan speed varies with load)
Noise (The value
changes with the
different load and
temperature at the
60
place 1 meter
away from the
equipment) dB
Others
Mean time
between failures
200,000 hours
(MTBF)
Protection grade
IP20
(EN60529)
Incoming line way
Lower wiring pattern
Standards
IEC62040-1-1
、
EN62109-1:2010, EN62109-2:2011,
Dimensions (W*D*H)
600mm*700 mm *1750 mm
Packing (W*D*H)
690mm*790 mm *1850 mm
Weight
250
280
300
320
345
360
Table 11 Specifications of Product