CENTAURI ENERGY SERVER
User Manual - Model 30-2017/12/18-VERSION 1.0
24
When the maintenance work is complete, the state of no fault protection of AC power for
the load is switched into the state with the power supply protection by the Server by
conducting the following steps.
1.
Carefully confirm that there is nothing left in the cabinet of the Server and the internal
connecting wires of the Server recover to the state before the maintenance.
2.
Boot the system in the same way of “Booting Steps", at this moment, the Server is in
standby state and the "INV LED" LED flashes;
3.
Turn off the maintenance bypass switch and then put on the dismantled buckle in place.
4.
Click "
" button on the main interface→ "User Setup" button→ and input the
password (the default password is “88888888”) and then click "
" button, and then
enter " INV " setup interface → " Manual Bypass" interface successively to select "OFF"
option and click "OK" button. At this point, the system exits the maintenance mode to
put an end to the maintenance work, and the load is powered up by the Server instead of
the bypass system.
3.5
System Setup
(Click “
” button to enter the system setup interface)
3.5.1
Advanced Setup
(Click the "Advanced Setup" button and enter the advanced setup interface by entering the
advanced password, which is only done by the authorized technical personnel).
3.5.1.1
Setup of System Mode
Click the "System Setup" button to enter the "Working Mode", then "Grid-connected/ off-
grid" mode or "off-grid" mode and the operation will be effective after confirmation.
3.5.1.2
PV Auto Power-on Setting
PV automatic power-on: When the PV automatic power-on mode is set to the “ON”
state and the automatic power-on operation can be done in the following two
situations.
1.
After the battery low voltage protection is shut down, the system will execute the
automatic power-on command when the MPPT is sufficient.
2.
After the system sends the fault information and is shut down, the system
automatically clears away the fault once when the PV is sufficient.
Operation steps of PV automatic power-on: Click the “PV automatic Power-on" button
to turn on or turn off this function. The system is in “ON” status by default.
3.5.1.3
Power-On Setting