CENTAURI ENERGY SERVER
User Manual - Model 30-2017/12/18-VERSION 1.0
22
Warning!
If necessary, please disconnect the connection of the lower load and then paste the
warning sign on the joint of the load.
The component with its protective cover plate opened with the tool is the part which
the user cannot operate.
Only the maintenance support personnel authorized by the Company can
open the protective cover plate of such products.
3.1.1
Booting Steps
1.
Switch on the output switch of the battery box (battery pack);
2.
Switch on the input switch of the external power (RECTIFIER, BYPASS) of the Server;
3.
Switch on the DC START switch of the Server;
4.
Switch on the RECTIFIER and BYPASS switches of the Server;
5.
Switch on the switches of "PV 1 # - PV 4 #" in turn.
6.
Press the "INV ON" button of the panel and confirm the dialogue information of the
touch screen (Touch operation: Click the “
” button on the main interface and then
select the “Boot” option and click “OK” button) to boot the machine.
7.
Switch on the output switch.
3.1.2
Shutdown Steps
1.
Press the "INV OFF" button of the panel and confirm the dialogue information of the
touch screen (Touch operation: Click the “
” button “OFF” button and “OK” button
in turn), the system will switch off the machine.
2.
Turn off the output switch.
3.
Switch off the switches of "PV 1 # - PV 4 # " in turn;
4.
Switch off the RECTIFIER and BYPASS switches of the Server;
5.
Switch off the DC START switch of the Server;
6.
Switch off the RECTIFIER and BYPASS input switches of the external power of the
Server;
7.
Switch off the switches of the battery box (battery pack).
3.2
Emergency Stop Operation
In case of an emergency (such as an electric shock, a fire, a flood, etc.), please press the red
"EPO" button on the panel to perform the emergency stop command. After the button is
pressed, the system immediately cuts off all the outputs (including the Server output and
the bypass output, battery charging or discharging). When the machine is shut down, please
perform "OFF" operation and then conduct the “ON” operation when the display screen and
LED of the system are fully closed, please pay attention to all operations above.
3.3
Clear Operation for System Fault
When the Server is shut down due to any reason, including, but not limited to disabled over-
temperature protection of the rectifier and the Server, overload being more than or equal
to 150%, busbar instantaneous overvoltage, abnormal protection, etc., please confirm that