Incoming Line Way of System
The incoming lines of the Server is the lower wiring pattern. When wiring, open the front
door of the Server, unpack the downside baffle, you can view the connection bar connected
with the power cable.
2.7
Requirements of External Distribution
To guarantee reliable operation of the Server, please make sure that the power of
the external power supply should be more than 1.5 times of the equipment’s rated
power and the rated current of the power circuit breaker supply nearby the supply
equipment should be more than 1.2 times (not the switch with one grade higher
than the breaker) of that of the air switch of the equipment itself (RECTIFIER or
BYPASS).
The "BYPASS INPUT" and "AC INPUT” power supply system of the equipment should
be equipped with the separate "Circuit Breaker" or "Over-current Protection Switch” in
order to improve the reliability of the system.
The external power switch should be installed near the system to cut off the power
supply in an emergency.