4.3
Off-peak Power Consumption
1.
Limited current charging: After set up of the limited current charging of the system, the
system will shut off the charging function of the rectifier within the set time, in this time
the PV will supply power to the load at first, and the extra power will be used to charge
the battery. If PV power is not enough, AC will help to supply power to the load. Out of
the limited current set time, the rectifier charge function will recover to charge the
battery.
Fig 12 Mode 1 for Off-peak Electricity Consumption
2.
Off-peak of electricity consumption: After the off-peak electricity consumption is set up,
the system will shut off the rectifier within the limit time, the PV and the battery will
provide the power to the loads until the battery discharges and then the system
automatically enters the limited current charging mode;
Fig 13 Mode 2 for Off-peak Electricity Consumption
3.
After the peak of electricity consumption; the system will start the function of the
rectifier to recharge the battery based on setting of the use, and the loads are also
powered by the rectifier;