107
Operation denied
(RISE TIME/SIM/SEQ)
Operation is denied because soft start, power line abnormality
simulation, or sequence is in progress.
108
Operation denied
(WIRing METHod)
Operation is denied because the wiring method (single-phase,
two-wire; single-phase, three-wire; or three-phase) is invalid.
109
Operation denied
(EXT.OUTPUT OFF)
Operation is denied because the output has been turned off
through external control.
110
Operation denied
(EXT.SEQ.STOP)
Operation is denied because a sequence is being executed or
stopped through external control.
111
Operation denied (V-
PROG)
Operation is denied because the AC voltage output is being
controlled with an external signal.
112
Operation denied
(SOURCE)
Operation is denied because the command is in conflict with the
signal source setting.
199
Operation denied
(BUSY)
The operation is denied because the PCR-LE/PCR-LE2 is busy.
201
Operation denied
(FREQ)
The sequence cannot be executed because there is a step
whose frequency is outside its limits.
202
Operation denied
(VOLT)
The power line abnormality simulation, or the sequence cannot
be executed because there is a step whose voltage is outside
the voltage range or limits.
203
Operation denied
(PHASE CHANG)
The sequence cannot be executed because there is a step
whose trigger wait setting and sudden phase change setting are
both turned on.
301
Settings conflict
(COMPENSATION)
Setting conflict: Cannot be set because the command is in
conflict with the compensation setting.
302
Settings conflict (CV
RESPONSE)
Setting conflict: Cannot be set because the command is in
conflict with the response setting.
303
Settings conflict (RISE
TIME)
Setting conflict: Cannot be set because the soft start output is
in progress or the command is in conflict with the soft start
setting.
304
Settings conflict
(SYNCRO)
Setting conflict: Cannot be set because the synchronization
function is in use.
305
Settings conflict
(TRIP)
Setting conflict: Cannot be set because the command is in
conflict with the action that is performed when any of the
current limits is exceeded.
306
Settings conflict
(UNBALANCE PHASE)
Setting conflict: Cannot be set because the phase difference is
unbalanced.
308
Settings Conflict
(OUTPUT
IMPEDANCE)
Setting conflict: Cannot be set because an output impedance is
set.
309
Settings conflict
(WAVE BANK)
Setting conflict: Cannot be set because a waveform other than
waveform bank No. 0 is in use.
909
Selftest error (DSP
SIO)
Self-test error: Detected an error in the internal
communication.
910
Selftest error (DSP
DETect)
Self-test error: Detected an input voltage outside the ratings at
power-on.
911
Selftest error (DSP
VCC)
Self-test error: Detected a voltage error.
912
Selftest error (DSP
Input)
Self-test error: Detected an input voltage outside the ratings.
913
Selftest error (DSP
CMD)
Self-test error: Detected an invalid internal communication
command.
915
Selftest error (CAL)
Self-test error: Detected an error in the calibration data.
PCR-M series Communication Interface Manual
KIKUSUI ELECTRONICS CORP.
52/166