Installation
July 2018
4-28
06-237518-001
4-13.2
Cylinder
Each cylinder shall be labelled with the following:
•
Agent Instruction label: This labels shall be attached on the front of the cylinders and at
same height. The purpose of the label is to provide filling information, transport/safety in-
formation, inspection information and general precautions to be taken during re-installation
of the cylinder.
•
Agency Label: Label listing the approving agencies.
•
Transport label: Commonly referred to as a banana label which is curved and located on
the cylinder shoulder
4-13.3
Selector Valves
Each selector valve shall be provided with a sign or label clearly stating the name of the
associated protected space to which the valve shall conveys the Agent.
4-13.4
Protected Enclosure
4-13.4.1 Access Doors
Doors leading to and from the protected area to be fitted with appropriate signs (P/N K4076-
2), or signs in local language with same text that comply with associated National Standards.
All doors from an area protected by a gaseous extinguishing system should open outwards and
be fitted with automatic door closing devices.
4-13.5
Warning Alarms
Audible and visual alarms to be provided within the protected space, such alarms shall continue
to operate after discharge until all appropriate action has been taken.
4-13.5.1 Pressure Relief Vents
Relief vent openings (except at high level) to display warning sign, “Vent for Inert Gas - Keep
Clear” (P/N 2172-0200).
Summary of Contents for 400 Series
Page 2: ...Table i Revision History Revision Change Description AA Initial Release ...
Page 16: ...July 2018 xiv 06 237518 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 157: ...06 237518 001 A 1 July 2018 APPENDIX A SAFETY DATA SHEETS ...
Page 188: ...July 2018 A 2 06 237518 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 189: ......