Component Descriptions
July 2018
2-8
06-237518-001
2-3.6
Pilot Line Non-Return Valve
Use the pilot line non-return valve (P/N 38-400002-003) in the pilot lines of systems protecting
multiple hazards to isolate sections of the cylinders. Activating cylinders downstream of the
pilot line non-return valve will not activate cylinders upstream, preventing excess agent from
being discharged into a hazard.
Figure 2-9. Pilot Line Non-Return Check Valve
Figure 2-10. Pilot Line Non-Return Check Valve Direction of Flow
Figure 2-11. Typical Pilot Line on Selector Valve System (Rear View)
Table 2-6. Components for Typical Pilot Line
Item
Description
1
Hazard 1 Release Unit
2
Hazard 2 Release Unit
3
Pilot Line Non-Return Valve
4
Pilot Line Bleed Valve
From Release Unit on Cylinder
To Cylinder valve
From Previous Cylinder
Valve Upstream
To Distribution
Pipe Work