System Design
July 2018
3-22
06-237518-001
3-17.3
Pipe Sizing
The following table may be used as an estimating guide for sizing distribution piping. This table
is intended for use as a guide only. Use the Kidde IGS Flow Calculation software for the final
design.
Note:
For a 120 second discharge, use one pipe size less than the size shown in Table 3-17.
3-17.4
Other Conditions
3-17.4.1 Operating/Storage Temperature Range
The
Kidde IGS equipment listed herein is designed to operate within the range of
-20°C to 50°C (-4°F to 122°F). The Kidde IGS Flow Calculation software assumes a
temperature of 20°C (68°F).
3-17.4.2 Storage Temperature
Kidde IGS equipment is suitable for storage from -20°C to 50°C (-4°F to 122°F).
Table 3-17. Pipe Size vs. Flow Rate
Pipe
Dimensions
Standard
DIN 2442
DIN 2448
DIN 2458
Sch. 40
BS 10255
Kg/minute
Kg/minute
Kg/minute
Kg/minute
Kg/minute
½”
1 – 25
1 – 25
1 – 25
1 – 30
1 – 30
¾”
25 – 50
25 – 50
25 – 50
30 – 50
30 – 50
1”
50 – 80
50 – 80
50 – 80
50 – 85
50 – 85
1 ¼”
80 – 145
80 – 145
80 – 145
85 - 150
85 - 150
1 ½”
145 – 190
145 – 190
145 – 190
150 – 200
150 – 200
2”
190 – 320
190 – 320
190 – 320
200 – 335
200 – 335
2 ½”
320 – 550
320 – 550
320 – 550
335 – 475
335 – 475
3”
550 – 760
550 – 760
550 – 760
475 – 740
475 – 740
3 ½”
N.A.
N.A.
N.A.
740 – 990
N.A.
4”
780 – 1260
780 – 1260
780 – 1260
990 – 1275
990 – 1275
5”
1260 – 1870 1260 – 1870 1260 – 1870
1275 - 2000
1275 - 2000
6”
1870 – 2800 1870 – 2800
1870 - 2800
2000 - 3000
2000 - 3000
Summary of Contents for 400 Series
Page 2: ...Table i Revision History Revision Change Description AA Initial Release ...
Page 16: ...July 2018 xiv 06 237518 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 157: ...06 237518 001 A 1 July 2018 APPENDIX A SAFETY DATA SHEETS ...
Page 188: ...July 2018 A 2 06 237518 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 189: ......