Post-Discharge Maintenance
July 2018
7-4
06-237518-001
7-5
RE-INSTALLING SLAVE CYLINDER GAUGE ASSEMBLIES
Follow this procedure when re-installing the slave cylinder gauge assembly:
Note:
Slave Cylinder Gauge Assemblies must be replaced as a whole unit. There are no indi-
vidual serviceable parts on the unit apart from the connector O-ring. When reinstalling
the slave cylinder gauge assembly, the O-ring must be replaced.
1. Remove the old O-ring in the connecting swivel and replace it with one of the O-rings in-
cluded in the rebuild kit, P/N: 38-400001-010. Make sure the O-ring is properly lubricated
before installation. If lubrication is missing, use silicone spray (Würth Art no: 0893221 or
similar).
2. Installing slave cylinder gauge assemblies, applying a torque of 45 ± 1Nm. A counter hold
may be required.
3. Leak test all connections on the slave cylinder gauge assembly by means of ammonium-
free leak detection liquid or spray, ensuring that there is no leakage.
Note:
The pre-assembled unit shall not be tampered with, as any adjustment to components
pre-fitted to the connector block will lead to a leak.
7-6
RECHARGING KIDDE IGS SYSTEM CYLINDERS
After a fire, contact Kidde Fire Protection or authorised distributor for service replacements or
refilling of cylinders.
CAUTION
Only the O-ring should be lubricated. Excessive lubricant in the valve port will
enter into the valve itself when pressurized and may jeopardize the
performance.
Summary of Contents for 400 Series
Page 2: ...Table i Revision History Revision Change Description AA Initial Release ...
Page 16: ...July 2018 xiv 06 237518 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 157: ...06 237518 001 A 1 July 2018 APPENDIX A SAFETY DATA SHEETS ...
Page 188: ...July 2018 A 2 06 237518 001 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 189: ......