BOP HIPWR 031912
1-3
OUTPUT CHARACTERISTICS (Continued)
Digital Programming
resolution / accuracy
Voltage
14 bits / 0.03%
3% accuracy for Ext Ref Level (see PAR.
3.4.3.2). Unit gain adjustable between 0 and
EO
NOM
(voltage) or IO
NOM
(current).
Current
14 bits / 0.1%
Voltage Limit
12 bits / 0.3%
Current Limit
12 bits / 0.5%
Digital Readback
resolution / accuracy
Voltage
16 bits / 0.05%
main or limit channel
Current
16 bits / 0.1%
main or limit channel
Sustain Output
update rate
400 updates/Sec
voltage or current
Analog Programming
accuracy
Voltage
0.1% of rating
Current
0.1% of rating
Voltage Limit
0.3% of rating
10% to 100% of nominal range, converted to
digital at 100mS rate.
Current Limit
0.5% of rating
Analog Readback
accuracy
Voltage
-
Available on request: 0 to ±10V for 0 to ±nom-
inal output voltage.
Current
0.1% of rating
0 to ±10V for 0 to ±nominal output voltage.
Digital Readback
Characteristics
measurement rate
5 ms
measurement array
64 samples
voltage and current
step change timing
40
µ
S (default)
Allows rejection of line-related ripple/noise by
changing response time for output step
change (see PAR. B.9).
Voltage stabilization in
voltage mode
source effect
0.05% of rating
min-max input voltage
load effect
0.1% of rating
0-100% load current
time effect (drift)
0.02% of rating
0.5 through 8 hours
temperature effect
0.02%/deg C of rating
0 to 50 deg C
ripple and noise (2% EOmax) p-p/(0.2% EOmax) rms Includes switching noise
Current stabilization in
current mode
source effect
0.05% of rating
min-max input voltage
load effect
0.2% of rating
0-100% load voltage
time effect (drift)
0.02% of rating
0.5 through 8 hours
temperature effect
0.02%/deg C of rating
0 to 50 deg C
ripple and noise
2% IOmax p-p / (0.2% IOmax) rms Includes switching noise
Error sensing
0.25V or 1% of voltage rating per
wire (whichever is less)
Above rated output1
Transient recovery in
voltage mode
maximum excursion
5% of nominal output
nominal voltage, 50% load step
Recovery time
200
µ
S
Return within 0.1% of set voltage
Output Common Mode Voltage
300V
Output to chassis ground
Series operation
Master/slave
Maximum of identical 3 units,
up to 300V max.
Parallel operation
Master/slave
Maximum of 5 identical units
Series-parallel Operation
2 series x 2 parallel
3 series x 2 parallel
Master/slave for both series and parallel
branches of identical units
1. Remote error sensing applies to the main voltage channel. Feedback for the ±voltage limit channels is supplied locally
from the power terminals. Consult factory for a remote sensing solution applicable to the voltage limit channels.
TABLE 1-2. BOP GENERAL SPECIFICATIONS (Continued)
SPECIFICATION
RATING/DESCRIPTION
CONDITION
Summary of Contents for BOP-MG
Page 2: ......
Page 10: ......
Page 20: ...x BOP 1K 031912 FIGURE 1 1 HIGH POWER BOP SERIES POWER SUPPLY...
Page 37: ...BOP HIPWR 031912 1 17 FIGURE 1 3 BOP OUTPUT CHARACTERISTICS...
Page 53: ...BOP HIPWR 031912 2 15 FIGURE 2 4 PARALLEL CONFIGURATION LOCAL SENSING TYPICAL...
Page 54: ...2 16 BOP HIPWR 031912 FIGURE 2 5 PARALLEL CONFIGURATION REMOTE SENSING TYPICAL...
Page 64: ......
Page 132: ......
Page 192: ......