Connections and wiring
Project engineering manual V1.00
42
© KEBA
Protective earth conductor with mains cable crosssection < 10
mm²
Illustration 619: Double protective earth conductor
1
... D3DU 3xx/x control module
2
... D3DP 3xx/x supply module
3
... D3DA 3xx/x axis module
4
... Mains filters
5
... Mains choke
6
... Double protective earth conductor
connection
7
... Protective earth (PE)
6.2
Electrical isolation concept
All control terminals are designed as safety extralow voltage/protective ex
tralow voltage (SELV/PELV) circuits and must only be operated with such
SELV/PELV voltages, as per the relevant specification. This provides reli
able protection against electric shock on the control side.
The 24 V power supply necessary for the PELV circuit is provided by the
supply module D3DU 3xx/x via the busbars 24 V DC / GND. The following
overview shows the potential supplies for the individual terminals in detail.
This concept also delivers higher operational safety and reliability of the axis
modules and the controller.
Summary of Contents for D3DP 3 Series
Page 1: ...D3 DP 3xx x Supply module Project engineering manual V 1 00 Translation of original manual ...
Page 4: ...D3 DP 3xx x Project engineering manual V1 00 4 KEBA ...
Page 8: ...D3 DP 3xx x Table of Contents Project engineering manual V1 00 8 KEBA ...
Page 75: ...D3 DP 3xx x Declaration of conformity Project engineering manual V1 00 75 KEBA ...
Page 76: ...D3 DP 3xx x Declaration of conformity Project engineering manual V1 00 76 KEBA ...
Page 77: ...D3 DP 3xx x Declaration of conformity Project engineering manual V1 00 77 KEBA ...
Page 80: ...D3 DP 3xx x Glossary Project engineering manual V1 00 80 KEBA Glossary ...
Page 81: ...D3 DP 3xx x Index Project engineering manual V1 00 81 KEBA Index ...
Page 82: ...D3 DP 3xx x Index Project engineering manual V1 00 82 KEBA ...