Operating Instructions CDF3000
4-19
4 Commissioning
DE
EN
FR
IT
ES
FR
Result:
If the step response of your drive does approximately correspond with the
illustration, it is assured that the motor phases are correctly wired, the
encoder is correctly connected and the CDF3000 is parameterized to the
correct motor.
If the step response deviates considerably from the illustration, it is to be
assumed that
•
the motor dataset was incorrectly selected or
• that the wiring is incorrect.
Check the individual steps from Chapter 3 "Installation" and Chapter 4.3
"Initial commissioning" and repeat the test run.
The step response may also deviate if the ratio of the machine moment of
inertia reduced onto the motor shaft relative to the motor moment of iner-
tia is very high. Here the loop control settings must be optimized. For spe-
cial settings to optimize the speed and position control loops, please use
the CDF3000 Application Manual.