Insulation Work
Installation
69
9. Engineering of insulation
9.1 Insulation of refrigerant pipe
9.1.1 Operational procedure of refrigerant pipe insulation
Cut the suitable pipe
→
insulation (except joint section)
→
flare the pipe
→
piping layout and connection
→
vacuum drying
→
insulate the joint parts
9.1.2 Purpose of refrigerant pipe insulation
During operation, temperature of gas pipe and liquid pipe shall be over-heating or over-cooling
extremely. Therefore, it is necessary to carry out insulation; otherwise it shall debase the performance
of unit and burn compressor.
Gas pipe temperature is very low during cooling. If insulation is not enough, it shall form dew and cause
leakage.
Temperature of gas pipe is very high (generally 50-100
) during heating. Insulation work must be
carried out to prevent hurt by carelessness touching.
9.1.3 Insulation material selection for refrigerant pipe
The burning performance should over 120
According to the local law to choose insulation materials
The thickness of insulation layer shall be above 10mm.If in hot or wet environment place, the layer of
insulation should be thicker accordingly.
9.1.4 Installation highlights of insulation construction
Gas pipe and liquid pipe shall be insulated separately, if the gas pipe and liquid pipe were insulated
together; it will decrease the performance of air conditioner.
Liquid pipe
Insulation meterial
Gas pipe
The insulation material at the joint pipe shall be 5~10cm longer than the gap of the insulation material.
The insulation material at the joint pipe shall be inserted into the gap of the insulation material.
The insulation material at the joint pipe shall be banded to the gap pipe and liquid pipe tightly.
The linking part should be use glue to paste together
Be sure not bind the insulation material over-tight, it may extrude out the air in the material to cause bad
insulation and cause easy aging of the material.
9.2 Insulation of drainage pipe
9.2.1 Operational procedure of refrigerant pipe insulation
Select the suitable pipe
→
insulation (except joint section)
→
piping layout and connection
→
drainage test
→
insulate the joint parts
Summary of Contents for Zen On 2014
Page 1: ...Contents i Service Manual 2014 ...
Page 2: ......
Page 3: ...Contents i ...
Page 4: ......
Page 6: ......
Page 18: ...Wiring Diagrams 12 Duct Type 4 Wiring Diagrams KPD 140 HN6 KPD 176 HN6 ...
Page 24: ...Field Wiring 18 Duct Type 10 Field Wiring KPD 140 HN6 KPD 176 HN6 ...
Page 41: ...Service Space Ceiling Floor Type 35 3 Service Space ...
Page 42: ...Wiring Diagrams 36 Ceiling Floor Type 4 Wiring Diagrams KPC 140 HN6 KPC 176 HN6 ...
Page 45: ...Field Wiring Ceiling Floor Type 39 9 Field Wiring KPC 140 HN6 KPC 176 HN6 ...
Page 50: ...Wiring Diagrams 44 Outdoor Units 4 Wiring Diagrams KUE 140 HTN6 KUE 176 HTN6 ...
Page 95: ...Troubleshooting Electrical Control 89 f Indoor fan speed has been out of control Eb ...
Page 98: ...Troubleshooting 92 Electrical Control c Up down panel is not closed ...
Page 103: ...Controller Electrical Control 97 3 Controller 3 1 KI 01 Wireless Remote Controller Optional ...
Page 115: ......
Page 116: ......