Electrical Control Function
Electrical Control
77
For Ceiling & Floor:
T3
TE10
Off
On
TE11
When T3
≥
TE10, the compressor will shut off. When T3
<
TE11,the compressor will restart.
1.3.3 Heating Mode
1.3.3.1 Compressor running rules:
For Duct & super-slim cassette type: Once the compressor starts up, it keeps running 7 minutes,
For Ceiling & Floor
: Once the compressor starts up, it keeps running HEATFTIM minutes,
then it will follow the below rules:
When indoor room temp.T1 is higher than Tgap0, the compressor and outdoor fan will shut off. When T1 is
lower than Tgap0-1, the compressor and outdoor fan will start up.
Tgap0
T1-TS
On
Off
Tgap0-1
For Ceiling & Floor:Tgap0
= setting temperature-compensation.
1.3.3.2 Outdoor fan running rules:
Fan(below): The outdoor fan runs all the time.
Fan(above):
18
T4
Off
On
16
1.3.3.3 Indoor fan running rules:
When the compressor is on, the indoor fan can be set to high/med/low/auto. And the anti-cold wind function
has the priority.
Summary of Contents for Zen On 2014
Page 1: ...Contents i Service Manual 2014 ...
Page 2: ......
Page 3: ...Contents i ...
Page 4: ......
Page 6: ......
Page 18: ...Wiring Diagrams 12 Duct Type 4 Wiring Diagrams KPD 140 HN6 KPD 176 HN6 ...
Page 24: ...Field Wiring 18 Duct Type 10 Field Wiring KPD 140 HN6 KPD 176 HN6 ...
Page 41: ...Service Space Ceiling Floor Type 35 3 Service Space ...
Page 42: ...Wiring Diagrams 36 Ceiling Floor Type 4 Wiring Diagrams KPC 140 HN6 KPC 176 HN6 ...
Page 45: ...Field Wiring Ceiling Floor Type 39 9 Field Wiring KPC 140 HN6 KPC 176 HN6 ...
Page 50: ...Wiring Diagrams 44 Outdoor Units 4 Wiring Diagrams KUE 140 HTN6 KUE 176 HTN6 ...
Page 95: ...Troubleshooting Electrical Control 89 f Indoor fan speed has been out of control Eb ...
Page 98: ...Troubleshooting 92 Electrical Control c Up down panel is not closed ...
Page 103: ...Controller Electrical Control 97 3 Controller 3 1 KI 01 Wireless Remote Controller Optional ...
Page 115: ......
Page 116: ......