Troubleshooting
84
Electrical Control
For Ceiling & Floor
NO.
Malfunction
Running
lamp
Timer
lamp
Defrosting
lamp
Alarm
lamp
1
Communication malfunction between indoor and outdoor
units
☆
X
☆
X
2
Open or short circuit of T1 temperature sensor
X
☆
X
X
3
Open or short circuit of T2 temperature sensor
☆
X
X
X
4
Open or short circuit of T3 temperature sensor
X
X
☆
X
5
Outdoor unit malfunction
☆
☆
☆
☆
6
Indoor EEPROM malfunction
☆
☆
X
X
7
Full-water malfunction
X
X
X
☆
8
Indoor fan speed is out of control
X
☆
X
☆
9
Protection of low pressure
☆
☆
☆
X
LEDs’ for the indication of outdoor trouble
Type
Contents
LED2(Green)
LED3(Yellow)
LED4(Red)
Normal
Normal running
O
X
X
Normal
Normal standby
X
O
X
Trouble
Phase sequence error
X
☆
X
Trouble
Lack of phase
X
X
☆
Trouble
Open-circuit and short-circuit trouble of T3
X
X
O
Trouble
Open-circuit and short-circuit trouble of T4
☆
X
X
Trouble
Temperature protection of compressor
discharge
O
X
O
Trouble
Protection of high pressure
☆
☆
X
Trouble
Protection of low pressure
☆
X
☆
Trouble
Overload of current
X
☆
O
Trouble
High temperature protection of condenser
☆
☆
O
Trouble
Fan selection error
☆
☆
☆
O(light) X(off)
☆
(flash at 1Hz)
Note:
1. T3: Outdoor condenser temperature sensor
2. T4: Outdoor ambient temperature sensor
Summary of Contents for Zen On 2014
Page 1: ...Contents i Service Manual 2014 ...
Page 2: ......
Page 3: ...Contents i ...
Page 4: ......
Page 6: ......
Page 18: ...Wiring Diagrams 12 Duct Type 4 Wiring Diagrams KPD 140 HN6 KPD 176 HN6 ...
Page 24: ...Field Wiring 18 Duct Type 10 Field Wiring KPD 140 HN6 KPD 176 HN6 ...
Page 41: ...Service Space Ceiling Floor Type 35 3 Service Space ...
Page 42: ...Wiring Diagrams 36 Ceiling Floor Type 4 Wiring Diagrams KPC 140 HN6 KPC 176 HN6 ...
Page 45: ...Field Wiring Ceiling Floor Type 39 9 Field Wiring KPC 140 HN6 KPC 176 HN6 ...
Page 50: ...Wiring Diagrams 44 Outdoor Units 4 Wiring Diagrams KUE 140 HTN6 KUE 176 HTN6 ...
Page 95: ...Troubleshooting Electrical Control 89 f Indoor fan speed has been out of control Eb ...
Page 98: ...Troubleshooting 92 Electrical Control c Up down panel is not closed ...
Page 103: ...Controller Electrical Control 97 3 Controller 3 1 KI 01 Wireless Remote Controller Optional ...
Page 115: ......
Page 116: ......