Troubleshooting
88
Electrical Control
d. Indoor EEPROM malfunction(E7)
If the EEPROM chip
is welded on PCB,
replace the PCB
directly. Otherwise,
check whether the
EEPROM chip
plugged in PCB well?
Yes
No
Yes
Insert the EEPROM well
Replace the indoor PCB.
Shut off the power supply and
turn it on 5 seconds later. Is it
still displaying the error code?
e. Full-water malfunction(E8)
If the water-level switch
is inserted well?
No
Insert the water-level switch well
If the water-level switch
is broken?
Yes
Replace the water-level switch
If the water pump is
normal?
No
Replace the water pump
Yes
No
Yes
Check PCB board or replace the indoor main PCB
Summary of Contents for Zen On 2014
Page 1: ...Contents i Service Manual 2014 ...
Page 2: ......
Page 3: ...Contents i ...
Page 4: ......
Page 6: ......
Page 18: ...Wiring Diagrams 12 Duct Type 4 Wiring Diagrams KPD 140 HN6 KPD 176 HN6 ...
Page 24: ...Field Wiring 18 Duct Type 10 Field Wiring KPD 140 HN6 KPD 176 HN6 ...
Page 41: ...Service Space Ceiling Floor Type 35 3 Service Space ...
Page 42: ...Wiring Diagrams 36 Ceiling Floor Type 4 Wiring Diagrams KPC 140 HN6 KPC 176 HN6 ...
Page 45: ...Field Wiring Ceiling Floor Type 39 9 Field Wiring KPC 140 HN6 KPC 176 HN6 ...
Page 50: ...Wiring Diagrams 44 Outdoor Units 4 Wiring Diagrams KUE 140 HTN6 KUE 176 HTN6 ...
Page 95: ...Troubleshooting Electrical Control 89 f Indoor fan speed has been out of control Eb ...
Page 98: ...Troubleshooting 92 Electrical Control c Up down panel is not closed ...
Page 103: ...Controller Electrical Control 97 3 Controller 3 1 KI 01 Wireless Remote Controller Optional ...
Page 115: ......
Page 116: ......