Now the nominal width of the pipes is selected from di-
agram 1 and is entered in the plan.
950 l/h
950 l/h
1900
l/h
1900 l/h
3800
l/h
4750 l/h
5700 l/h
6650 l/h
3800 l/h
2850 l/h
1900 l/h
950 l/h
+
DN 15
DN 15
DN
15
DN 15
DN
20
DN 25
DN 25
DN 25
DN 20
DN 20
DN 15
DN 15
+
Step 4: Check of the pressure loss
The pressure loss at the extraction point with the larg-
est distance to the supply unit should not exceed 15%.
For the calculation, the fittings are replaced by a
straight pipe segment with the same stream resist-
ance. The values for this can be taken from Table 4.
The pipe length can be used to determine the pres-
sure loss from diagram 2.
Pressure loss section 7 - 6
Determining the piping length