• The following Kantech readers have been validated by UL for the UL 1076 Standard: P225W26,
P225KPW26, P225XSF, P225KPXSF, P325W26, P325KPW26, P325XSF, P325KPXSF and P600.
• All alarms shall be reported and acknowledged in the following priority:
Note:
To set these priorities, please adjust the Event Parameters, found in EntraPass System
• Fire alarm and industrial supervision where a risk of injury to persons, or damage or destruction of
property may be involved
• Hold-up or panic alarm
• Burglar alarm
• Watchman tour (Guard tour)
• Fire-alarm supervision
• Burglar-alarm supervision
• Industrial supervision where a risk of injury to persons, or damage or destruction of property will
not be involved.
If multiplex system signals are transmitted directly from the protected systems to the central super-
vising station and the loss of the channel prevents the receipt of signals from protective circuits beyond
the fault, the number of separate signals on a single channel shall be limited to 1000.
Minimum 4 hours of stand-by power provided by a standby rechargeable battery, rated 12V, 7Ah. Loss
of AC signal is transmitted immediately to the central station. Required use of Reader's LED (flashing) as
acknowledgement signal indicator.
Use EntraPass and under Definition/Alarm System/Door enable the option "Supervised door when
armed" when using the Reader's flashing LED to indicate the acknowlegdment signal. POE/POE+ feature
is not permitted for UL 1076.
FCC & IC
Operation is subject to the following two conditions: (1) this device may not cause harmful interference,
and (2) this device must accept any interference received including interference that may cause
undesired operation.
• This class B digital apparatus meets all requirements of the Canadian Interference Causing Equipment
Regulations CAN ICES-3 (B) / NMB-3 (B).
CE & RCM
• EN60950-1, EN50130-4:2011, EN61000-6-3. CE Compliance in accordance with applicable LVD and EMC
Directives.
• Australia/New Zealand: RCM Compliance.
© Copyright, 2016, all rights reserved
49
Summary of Contents for KT-1
Page 1: ......
Page 6: ...6 Copyright 2016 all rights reserved ...
Page 10: ...10 Copyright 2016 all rights reserved ...
Page 17: ...Wiring Charts KT 1 Inputs and Outputs View Copyright 2016 allrights reserved 17 ...
Page 18: ...KT 1 PCB Inputs and Outputs View Copyright 2016 all rights reserved 18 ...
Page 19: ...KT 1 EU Inputs and Outputs View Copyright 2016 allrights reserved 19 ...
Page 20: ...KT 1 PCB EU Inputs and Outputs View Copyright 2016 all rights reserved 20 ...
Page 32: ...Inputs for KT 1 Inputs for KT 1 PCB Copyright 2016 all rights reserved 32 ...
Page 50: ......