UL 1076 Compliance Notice
• The KT-1 is UL 1076 Listed as a Commercial Proprietary Control Unit Accessory and Proprietary Burg-
lar Alarm Unit (Section 83.2), with EntraPass and Redundant Server, alarm system features, KT-300,
KT-400 Controllers, Kantech ioProx Proximity readers, and TRex request to exit devices – other
sensor devices (temperature, water level, etc.) may be used as long as they are also UL 1076 Listed.
• The EntraPass and Redundant Server shall be running at all time, and manned 24 hours a day, 365
days a year – The EntraPass and Redundant Server will each have their own operator workstation.
• Data processing equipment and office appliance and business equipment used as central supervisory
equipment station shall be listed to Information Technology Equipment - Safety-Part 1: General
Requirements - UL 60950-1.
• Should the EntraPass and/or Redundant Server be replaced, a UL 60950-1 listed computer must be
used.
• The following recommended system requirements apply to the EntraPass Server, Redundant Server,
Video Vault, Card Gateway, SmartLink, and Workstation:
• Operating Systems: Windows® 2008/Windows 2012/Windows 7 Standard/Enterprise
Server Editions/Windows 8
• Processor: Dual Core
• 4 GB RAM
• Minimum free hard disk space: 20 GB
• Color depth: 24-bit (16 million colors), required for Video Integration only
• Screen resolution: 1024 x 768
• AGP or PCI Express 8X graphics card with 64 MB memory and DirectX 9.0 support
• Network Interface card: 10/100 Base-T network adaptor
Note:
Actual requirements may vary based on your operating system and configuration.
• The Central Supervisory Equipment shall employ supply line transient protection complying with the
Standard for Transient Voltage Surge Suppressors, UL 1449, with a maximum marked rating of 330 V.
• The Central Supervisory Equipment shall employ signal line Transient protection complying with the
Standard for Protectors for Data Communications and Fire Alarm Circuits, UL 497B, with a max-
imum marked rating of 50 V.
• The Central Supervisory Equipment shall employ that communication circuits and network com-
ponents connected to the telecommunications network shall be protected by secondary pro-
tectors for communication circuits. These protectors shall comply with the Standard for Secondary
Protectors for Communications Circuits, UL 497A. These protectors shall be used only in the pro-
tected site of the telecommunications network.
• The Central Supervisory Equipment shall be installed in a temperature controlled environment. A
temperature controlled environment is defined as one that can be maintained between 14° - 10°C
(55° - 95°F) by HVAC system. Twenty-four hours on standby power shall be provided for the HVAC
system. The standby power system for the HVAC system may be supplied by an engine driven gen-
erator alone. A standby battery is not required to be used.
• A marking to identify the application and signaling function of the product is located on the inside of
the unit (inner door sticker).
• For certified commercial proprietary control unit accessory applications, the requirements of UL
1076, Commercial Proprietary Control Unit Accessory also apply.
• The reader(s), that is(are) designated to arm or disarm the alarm system, must be within the secured
side of the customer premises.
© Copyright, 2016, all rights reserved
48
Summary of Contents for KT-1
Page 1: ......
Page 6: ...6 Copyright 2016 all rights reserved ...
Page 10: ...10 Copyright 2016 all rights reserved ...
Page 17: ...Wiring Charts KT 1 Inputs and Outputs View Copyright 2016 allrights reserved 17 ...
Page 18: ...KT 1 PCB Inputs and Outputs View Copyright 2016 all rights reserved 18 ...
Page 19: ...KT 1 EU Inputs and Outputs View Copyright 2016 allrights reserved 19 ...
Page 20: ...KT 1 PCB EU Inputs and Outputs View Copyright 2016 all rights reserved 20 ...
Page 32: ...Inputs for KT 1 Inputs for KT 1 PCB Copyright 2016 all rights reserved 32 ...
Page 50: ......