V. INSTALLATION AND START UP
INSTALLATION of INVENTORY CABINETS
1 .
Mount Main K1600 enclosure in safe location away from steam, vibration, and where
wide temperature changes may occur. IF RS232 communications are to be utilized
consideration should be given to the distance between the K1600 and the Host computer.
2 .
Install the KIO-12 or KIO-16 PNEUMATIC INPUT ENCLOSURE if required as shown on
PHYSICAL LAYOUT Data Sheet# DS-112590PLPN12 or #DS-011091PLPN16.
3 .
Any conduit or plumbing brought into the enclosure should comply with Nema-4
standards. Do not enter the enclosure from the top if possible. Top entry may tend to
leak and water damage will void warranty.
.
4 .
When providing openings in the cabinet, extreme care should be taken to cover all
components as metal shavings can cause shorts in the system.
5 .
A clean 120VAC power source should be provided from a dedicated circuit
breaker. This breaker must be on at all times and no other equipment may be powered
from it. A power conditioning unit may be required to reduce incoming line noise
depending on individual plant conditions.
6 .
Keep electrical connection clean and dress all wiring. Route electrical wiring away from
all enclosure equipment (along bottom or side of enclosure).
7 .
Do not use enclosure for any outside wiring or other electrical equipment. Do not use
enclosure as a pull box.
8 .
Enclosure doors should be secured at all times. This is to prevent outside contamination
and to stabalize internal temperature.