2 2
Programming cont.
ALARM SETPOINTS
NOTE: All alarm level setpoints are to be entered in G A L L O N values.
TO PROGRAM PRESS
MULTI-TANK SCREEN DISPLAYS SINGLE-TANK SCREEN DISPLAYS
ALARM
SETPOINTS
To program the alarm setpoints first display the current alarm points by pressing the
<ALARM>
button
from either the Multi-tank or the single tank screen.
From the Multi-tank Display first find the HI, MID or LOW level screen which displays the level value for
the tank channel number to be changed by pressing the
<ALARM>
button and the
<UP-DOWN SCROLL>
buttons. Then press the
<PROG>
button , the
<channel number>
for the alarm to be changed, and then
the
<ENTER>
button. The Single tank level alarm screen will then be displayed.
For example, if the LOW level setpoint is to be changed on tank channel number# 5 to 250
gallons then:
1. Press the
< ALARM>
button from the Multi-tank inventory display
2. Press the
<UP-DOWN SCROLL>
buttons until the screen displays the low level
value for tank channel #5
3. Press
<PROG>
and a flashing cursor appears at the middle of the bottom line.
4. Press the
<5>
on the keypad and the
<ENTER>
button.
1 *4000 <HI> 5* 5000
2 *2500 <Ga> 6* 5000
3*25000 7* 6500
4*39900 8* 2450
CHANNEL NUMBER
HI - LEVEL SETPOINT
TANK 1 ALARMS CH:1
LO LEVEL: 100 GALS
MD LEVEL: 1500 GALS
HI LEVEL: 4000 GALS
ALARM
1L100 <LO> 5L 500
2L 250 <Ga> 6L 500
3L 250 7L 650
4L 300 8L 245
ALARM