Installation and Start up cont.
Set the zero offsets of each transmitter on the K1600 by changing the display to the
Single-tank display by pressing the
<RUN/PAGE>
button on the Front Panel. The Single-
tank display will appear as shown.
SINGLE TANK DISPLAY
PRESS the
<TIME/ZERO>
button and the bottom line will change to display the ZERO OFFSET on
the left and the current Transmitter AtoD reading on the right.
SINGLE TANK ZERO OFFSET SCREEN
If the values shown for Zero and AtoD are different check the transmitter output to make sure
that it is 4.00 ma and refer to Programming and Changing Data -Transmitter Zero Offsets.
If pneumatic tank sensors and controls are used in conjunction with the KIO PNEUMATIC INPUT
ENCLOSURE the AUTO-ZERO function should be operating and the Zero Offset value displayed on
the left should be the same as the current transmitter ATOD value displayed on the right.
TANK 1 30 GAL.
CH: 1 *EMPTY* LEVEL
CREAM 0.998 SPGR
0% FULL
TANK 5 30 GAL.
CH: 1 **LO** LEVEL
CREAM 0.998 SPGR
ZERO 50 ATOD 57
XMTR ZERO IN
ATOD COUNTS
CURRENT XMTR
OUTPUT IN ATOD
COUNTS