3 2
Installation and Start up cont.
9 .
Connect incoming 120VAC power to AC input terminals (TB1) as shown on PHYSICAL
LAYOUT Data Sheets #DS-120590PLMA , #DS-112590PLPN12, #DS-011091PLPN16.
120 VAC L
- TERMINAL #1 (H)
120 VAC N
- TERMINAL #2 (N)
GROUND G
- TERMINAL #3 (G)
INSTALLATION OF 4-20MA TRANSMITTERS
If supplied by K SYSTEMS CORP. , see enclosed Manufacturer's manual or Data Sheet on
installation of tank transmitters.
INSTALLATION OF 4-20MA SIGNAL LINES
1 .
To connect incoming 4-20 MA sensor signal lines see the following Data Sheets:
Incoming signal lines must be connected in the positions as outlined on the Data Sheets.
Unpowered transmitters can use the 24VDC on-board power supply of the K1600.
Direct 4-20 ma signal wires - K1600 PHYSICAL LAYOUT
Data Sheet #DS-120590PLMA
- TRANSMITTER INPUT &
COMMUNICATION DATA
Data Sheet #DS-010291TMAD
2 .
Signal lines from the tank transmitters are to be installed to the input terminals as
as shown on the Data Sheet and in the order as they appear on the Multi-tank Inventory
screen. The input channels are positioned on the terminal strip in blocks of 4 terminals
from the bottom to top #1-16. Terminal Block #1 is stacked underneath TERMINAL
Block #2 and alternate similarly for 3-16. Odd numbered Blocks are under the even
numbered blocks. Removeable plug in terminals are provided to facilitate wire
installation. The first tank displayed in the CHannel #1 position on the Multi-tank
screen (upper left) is associated with Terminal Block #1 and so on.