2 6
Programming cont.
Example
: The tank on CHannel #5 is empty and the zero offset reads 50 but the
transmitter reads 57 AtoD counts. This means that the zero of the
transmitter has shifted upward from approx. 4.00 ma to approx. 4.028 ma.
TO PROGRAM PRESS
MULTI-TANK SCREEN DISPLAYS SINGLE-TANK SCREEN DISPLAYS
ZERO
OFFSET
VALUES
To program the transmitter zero offset, first display the current offset by pressing the
<TIME/ZERO>
button from either the Multi-tank or the single tank screen.
From the Multi-tank Display locate the zero value for the tank channel number to be changed. Then
press the
<PROG>
button , the
<channel number>
for the offset to be changed, and then the
<ENTER>
button. The Single tank zero offset screen will then be displayed.
1. Press the
<TIME/ZERO>
button from the Multi-tank inventory display
2. Press
<PROG>
and a flashing cursor appears at the middle of the bottom line.
3. Press the
<5>
on the keypad and the
<ENTER>
button.
CHANNEL NUMBER
XMTR ZERO OFFSET
IN ATOD COUNTS
1 50 ZERO 5 50
2 54 6 50
3 52 7 65
4 47 8 45
TIME
ZERO
TANK 1 42730 GAL.
CH: 1 **HI** LEVEL
CREAM 0.998 SPGR
ZERO 50 ATOD 57
ZERO OFFSET IN
ATOD COUNTS
XMTR READING IN
ATOD COUNTS
1 50 ZERO 5 50
2 54 6 50
3 52 7 65
4 47 8 45
TIME
ZERO