KNX/EIB
Switch Actuator with Secure
14
4.2. Parameter window “General”
The parameter window “General” will be shown in Fig. 4.2, here set product type and general
parameters, general parameters apply to every output.
Fig. 4.2 Parameter window “General”
Parameter “Product type”
The parameter sets the product type of the Switch Actuator with current detection, and selects the
option according to the type of product actually used. Options:
4-Fold Output
(apply to ARSA-04/16.S, ARSA-04/20.S)
8-Fold Output
(apply to ARSA-08/16.S, ARSA-08/20.S)
12-Fold output
(apply to ARSA-12/16.S, ARSA-12/20.S)
Parameter “Operation delay after bus recovery [10..250]”
The parameter determines the delay time to react after the bus voltage recovery (the delay time
after electrified) to avoid the malfunction of the bus and 220V AC caused by the simultaneously
working of various relays, excluding the initialization time (approx. 2 seconds) of the device.
Options:
10-250 s