KNX/EIB
Switch Actuator with Secure
56
5.3.2.
Monitoring function object of “Heating actuator”
Fig. 5.3.2 Monitoring function communication object “Heating actuator”
No.
Function
Object name
Data type Flags
DPT
8
Report fault
Output A-{{...}}
1bit
C,R,T
1.005 alarm
This object is enabled when selecting “enable” in the parameter “
Extension function
”, used to check
whether the room thermostat is under malfunction or not. It will go into the fault mode with “1”.
Table 5.3.2 Monitoring communication objects “Heating actuator”
5.3.3. Forced function object “Heating actuator”
Fig. 5.3.3 Forced function communication object “Heating actuator”
No.
Function
Object name
Data byte
Flags
DPT
17
Forced operation
Output A-{{...}}
1bit
C,W
1.003 enable
This object will be started when enabling the forced function. Start the forced mode with “1” and
the other behaviors will be ignored; end the mode with “0”.
Table 5.3.3 Forced function communication object “Heating actuator”