KNX/EIB
Switch Actuator with Secure
55
5.3. Communication object “Heating actuator”
5.3.1. General communication object “Heating actuator”
Fig. 5.3.1 General communication object “Heating actuator”
No.
Function
Object name
Data type
Flags
DPT
15
Continuous control
Output A-{{...}}
1Byte
C,W
5.001 percentage
This object will be enabled when selecting “1byte (continues)” in the parameter “Control telegram
is received as”, is used to receive the control command of 1Byte, with range from 0% to 100%: the valve
will be off with “0%”, on with “100%”.
5
On-Off
Output A-{{...}}
1bit
C,W
1.001 switch
This object will be enabled when selecting “1bit on-off control” in the parameter “Control telegram
is received as”, to receive the command of 1bit: off with “0”; on with “1”.
14
Status (continuous),1 byte
Output A-{{...}}
1Byte
C,R,T
5.001 percentage
This object will be enabled when selecting “yes, continues control value (1byte)” in the parameter
“Reply the status of channel for continuous control”, indicating the running status of the current valve
and the duty cycle of PWM.
6
Status (continuous),1 bit
Output A-{{...}}
1bit
C,R,T
1.001 switch
This object will be enabled when selecting “yes, 0% =‘0’, otherwise ‘1’ (1 bit)” or “yes, 0% =‘1’,
otherwise ‘0’ (1 bit)” in the parameter “Reply the status of channel for continuous control”, indicating the
running status of the current valve.
When selecting “yes, 0% =‘0’, otherwise ‘1’ (1 bit)”, the valve will be off with “0”, others with “1”;
selecting “yes, 0% =‘1’, otherwise ‘0’ (1 bit)”, the valve will be off with “1”, others with “0”
4
Switch status
Output A-{{...}}
1bit
C,R,T
1.001 switch
This object will be enabled when selecting “‘1’= contact close; ‘0’=contact open” or “yes, ‘0’=
contact close; ‘1’=contact open” in the parameter “Reply the status of contact state”; indicating the
contact position of the current relay.
Table 5.9 General communication objects “Heating actuator”