Table 19: EX Series Switch Environmental Tolerances (continued)
Environment Tolerance
Switch or
device
Seismic
Temperature
Relative Humidity
Altitude
Complies with
Telcordia
Technologies Zone
4 earthquake
requirements
Normal operation ensured
in temperature range of 32°
F (0° C) to 104° F (40° C)
Nonoperating storage
temperature in shipping
container: – 40° F (–40° C)
to 158° F (70° C)
Normal operation ensured
in relative humidity range
of 5% to 90%,
noncondensing
No performance
degradation up to
10,000 ft (3048 m)
EX9251
The
maximum
thermal
output is
1705
BTU/hour
(500 W).
Complies with Zone
4 earthquake
requirements as per
GR-63, Issue 4.
Normal operation ensured
in the temperature range
41° F (5° C) through 104°
F (40° C)
Normal operation ensured
in the relative humidity
range 10% through 85%
(noncondensing)
No performance
degradation up to
10,000 feet
(3048 meters)
XRE200
NOTE:
Install EX Series switches only in restricted areas, such as dedicated equipment rooms
and equipment closets, in accordance with Articles 110– 16, 110– 17, and 110– 18 of the
National Electrical Code, ANSI/NFPA 70.
General Site Guidelines
Efficient device operation requires proper site planning and maintenance and proper layout of the equipment,
rack or cabinet (if used), and wiring closet.
To plan and create an acceptable operating environment for your device and prevent environmentally
caused equipment failures:
•
Keep the area around the chassis free from dust and conductive material, such as metal flakes.
•
Follow prescribed airflow guidelines to ensure that the cooling system functions properly and that
exhaust from other equipment does not blow into the intake vents of the device.
•
Follow the prescribed electrostatic discharge (ESD) prevention procedures to prevent damaging the
equipment. Static discharge can cause components to fail completely or intermittently over time.
•
Install the device in a secure area, so that only authorized personnel can access the device.
54
Summary of Contents for XRE200 -
Page 1: ...XRE200 External Routing Engine Hardware Guide Published 2020 12 15...
Page 135: ...135...
Page 142: ...142...
Page 155: ...Jewelry Removal Warning 155...
Page 158: ...Operating Temperature Warning 158...
Page 168: ...DC Power Disconnection Warning 168...
Page 172: ...DC Power Wiring Sequence Warning 172...