7.5.4 Adjustable parameters
INSERT
PARAMETERS
SETTING OPTIONS
FACTORY SETTINGS
EXPLANATION
All inserts of
LB Management
Astro time shift
+/- 0 – 120 minutes
0 minutes
Its own astro time shift can be set for each switching time.
Astro time
Automatic location adjustment using location
function of the smart phone
Astro times reflect the sunrise and sunset times in the course of a calendar year.
All LB Management inserts
in combination with a
brightness / temperature
sensor
Sun protection value
4,000 – 80,000 lux
20,000 lux
The sun protection is executed if any specified sun protection value is exceeded for
more than 2 minutes. The sun protection is deactivated if the brightness undercuts the
specified sun protection value for longer than 15 minutes.
Note: A brightness / temperature sensor is necessary for this function.
Temperature threshold
Sun protection
Off.
5 – 50 °C
Off
If the temperature-dependent sun protection is activated, it is checked whether the
specified temperature threshold has been exceeded before executing the sun protec-
tion. If this is not the case, the sun protection is not executed until the temperature has
been exceeded.
Note: A brightness / temperature sensor is necessary for this function.
Twilight value
5 – 4,000 lux
10 lux
The twilight function is executed if any specified twilight value is undercut for more than
4 minutes. The twilight function is deactivated if the brightness exceeds the specified
twilight value for longer than 4 minutes.
Note: A brightness / temperature sensor is necessary for this function.
Dimming inserts
Maximum brightness
75 – 100 percent
100 percent
Specifies the maximum adjustable brightness.
Minimum brightness
Basic brightness
1 – 40 percent
5 percent
Specifies the minimum adjustable brightness.
Switch on brightness
0 – 100 percent
100 percent
Specifies the brightness when switching on.
Blind inserts
Travel time
1 – 600 seconds
120 seconds
Absolute time that the blind needs for the travel from the upper to the lower limit
position.
The input is strictly required if position travels should be performed in order to be able
to display and adjust the position value (in percent) using the app.
Slat reversal time / fabric tightening
time
0 milliseconds – 10 seconds
0 milliseconds
Absolute time for the reversal of blind slats. The fabric tightening time for the operation
of awnings can be adjusted here.
Minimum reversal time
0.3 – 10 seconds
1 second
Minimum pause time for direction change. The motors can be protected by increasing
the minimum reversal time.
Ventilation position
1 – 100 percent
100 percent
Specifies how far the blind travels from the upper limit position to the ventilation position.
Operating mode
Blinds
shutters,
awnings
Roller shutters
Specifies which shading system is used.
Drive function
Normal operation,
inverse operation
Normal operation
Specifies the operating mode.
170
THE CLEVER CONFIG APP
Summary of Contents for LB management
Page 1: ...21 LB Management...
Page 2: ...Company founder Albrecht Jung Ernst Paris 2 COMPANY...
Page 4: ...4 PREFACE...
Page 9: ...THE JUNG LB MANAGEMENT 9...
Page 11: ...THE JUNG LB MANAGEMENT 11...
Page 15: ...THE JUNG LB MANAGEMENT 15...
Page 17: ...THE JUNG LB MANAGEMENT 17...
Page 31: ...Casa Fonte Boa Portugal Photos Jose Campos USAGE SCENARIOS 31 USAGE SCENARIOS 31...
Page 33: ...01 04 04 04 01 02 03 USAGE SCENARIOS 33...
Page 43: ...EQUIPMENT OVERVIEW 43...
Page 51: ...LB MANAGEMENT LIGHT 51...
Page 111: ...LB MANAGEMENT SHADING 111...
Page 139: ...TEMPERATURE CONTROL 139...
Page 155: ...THE CLEVER CONFIG APP 155...
Page 173: ...OPERATION 173...