LB management
eNet radio centre plate
Activate lock-out
protection switch-
ing state
On, Off
Basic setting: Off
Defines the behaviour of the output on activating
the lock-out protection.
Deactivate lock-
out protection
switching state
On, Off
Basic setting: Off
Defines the behaviour of the output on deactivat-
ing the lock-out protection. Only visible when the
priority for the lock-out protection is 0.
Priority, restraint
0...4
Basic setting: 2
Specifies the priority for recalling and removing a
scene of type Restraint for the channel.
Activate forced
operation switch-
ing state
On, Off
Basic setting: On
Defines the behaviour of the output on activating
the forced operation.
Deactivate forced
operation switch-
ing state
On, Off
Basic setting: Off
Defines the behaviour of the output on deactivat-
ing the forced operation. Only visible when the
priority for the forced operation is 0.
Priority, wind
alarm
0...4
Basic setting: 3
Specifies the priority for recalling and removing a
scene of type Wind alarm for the channel.
Activate wind
alarm switching
state
On, Off
Basic setting: Off
Defines the behaviour of the output on activating
the wind alarm.
Deactivate wind
alarm switching
state
On, Off
Basic setting: Off
Defines the behaviour of the output on deactivat-
ing the wind alarm. Only visible when the priority
for the wind alarm is 0.
Priority, sun pro-
tection
0...4
Basic setting: 0
Specifies the priority for recalling and removing a
scene of type Sun protection for the channel.
Activate sun pro-
tection switching
state
On, Off
Basic setting: On
Defines the behaviour of the output on deactivat-
ing the sun protection. Only visible when the pri-
ority for the sun protection is 0.
Deactivate sun
protection switch-
ing state
On, Off
Basic setting: Off
Defines the behaviour of the output on deactivat-
ing the sun protection. Only visible when the pri-
ority for the sun protection is 0.
Priority, twilight
0...4
Basic setting: 0
Specifies the priority for recalling and removing a
scene of type Twilight for the channel.
Activate twilight
switching state
On, Off
Basic setting: On
Defines the behaviour of the output on activating
the twilight function.
Deactivate twi-
light switching
state
On, Off
Basic setting: Off
Defines the behaviour of the output on deactivat-
ing the twilight function. Only visible when the pri-
ority for the twilight function is 0.
Invert switching
output
On, Off
Basic setting: Off
Inverts the switching output from NO contact
function (factory setting) to NC contact function
Minimum switch-
ing repeat time
100 ms ... 10 sec
Basic setting: 100 ms
Limits the switching speed of the device by in-
creasing the value, in order to protect the load,
for example. Only when the set time has elapsed
is switching possible again. The last command
during the blocking time is executed after a delay.
The switching repeat time starts after each
switching operation.
27 / 29
32597903
07.08.2019
J0082597903