LB management
eNet radio centre plate
Parameters
Setting options, Basic
setting
Explanations
Behaviour after
the end of the
disabling function
no change
Last value
Down
up
Basic setting: No
change
Behaviour of the output when a block is removed.
Manual saving of
the scene values
On, Off
Basic setting: On
Disables the saving of the current Venetian blind
position as scene value in an actuator for a com-
mand via a transmitter.
Disable wind
alarm via exten-
sion
On, Off
Basic setting: Off
If the function is switched on, the UP signal no
longer has increased priority via an extension
and can be stopped via local control or radio con-
trol.
Note: In order to be able to use the wind alarm
function via the extension, this function must be
switched on.
Priority, lock-out
protection
0...4
Basic setting: 1
Specifies the priority for recalling and removing a
scene of type Lock-out protection for the channel.
Activate lock-out
protection blind
position
0 ... 100 %
Basic setting: 0 %
Defines the behaviour of the output on activating
the lock-out protection.
Activate lock-out
protection slat
position
0 ... 100 %
Basic setting: 0 %
Defines the slat position of the output on activat-
ing the lock-out protection. Only visible when the
Venetian blind operating mode is set.
Deactivate lock-
out protection
blind position
0 ... 100 %
Basic setting: 0 %
Defines the behaviour of the output on deactivat-
ing the lock-out protection. Only visible when the
priority for the lock-out protection is 0.
Deacitvate lock-
out protection slat
position
0 ... 100 %
Basic setting: 0 %
Defines the behaviour of the output on deactivat-
ing the lock-out protection. Only visible when the
priority for the lock-out protection is 0 and the
Venetian blind operating mode is set.
Priority, restraint
0...4
Basic setting: 2
Specifies the priority for recalling and removing a
scene of type Restraint for the channel.
Activate force op-
eration blind posi-
tion
0 ... 100 %
Basic setting: 0 %
Defines the behaviour of the output on activating
the forced operation.
Recall forced op-
eration slat posi-
tion
0 ... 100 %
Basic setting: 0 %
Defines the slat position of the output on activat-
ing forced operation. Only visible when the Vene-
tian blind operating mode is set.
Deactivate force
operation blind
position
0 ... 100 %
Basic setting: 0 %
Defines the behaviour of the output on deactivat-
ing the forced operation. Only visible when the
priority for the forced operation is 0.
Deacitvate forced
operation slat po-
sition
0 ... 100 %
Basic setting: 0 %
Defines the slat position of the output on deactiv-
ating forced operation. Only visible when the pri-
ority for the forced operation is 0 and the Vene-
tian blind operating mode is set.
Priority, wind
alarm
0...4
Basic setting: 3
Specifies the priority for recalling and removing a
scene of type Wind alarm for the channel.