LB management
eNet radio centre plate
Parameters
Setting options, Basic
setting
Explanations
Deacitvate twi-
light slat position
0 ... 100 %
Basic setting: 0 %
Defines the slat position of the output on deactiv-
ating the twilight function. Only visible when the
priority for the twilight function is 0 and the Vene-
tian blind operating mode is set.
Channel settings "Swi fan"
Parameters
Setting options, Basic
setting
Explanations
Switch-off delay
0 s … 24 h
Basic setting: 0 s
The load switches off after a delay. Repeated
switch-off commands restart the delay time. If the
load has not yet been switched off due to the
delay when a switch-on command comes, then
the load will remain on.
Run-on time
0 s … 24 h
Basic setting: 0 s
If a run-on time is entered and the "Use run-on
time" parameter is activated, the actuator no
longer remains permanently switched on, but
only for the duration of the run-on time entered
here or transmitted by a motion detector. The
run-on time is restarted if actuation is repeated.
A motion detector command without transmitted
run-on time (e.g. from an extension) leads to
switching on for the duration of the run-on time
entered here. If no run-on time is entered here,
the default run-on time of 2 minutes is applied.
Use run-on time
On, Off
Basic setting: Off
On:
If a run-on time is configured (≠ 0 s), in addition
to motion detector commands, all switching or
dimming commands also lead to switching on for
the duration of the run-on time.
If no run-on time is configured (= 0 s), all switch-
ing or dimming commands result in permanent
switching of the load.
As soon as the attachment receives a motion de-
tector command, the transmitted run-on time is
automatically entered in the "Run-on time" para-
meter and this then also applies to all switching
and dimming commands.
Off:
Only motion detector commands lead to switch-
ing on for the duration of the transmitted or set
run-on time. The load is permanently switched for
switching and dimming commands.
Manual switch-off
of the run-on time
On, Off
Basic setting: Off
Allows manual switch-off of a running run-on
time. If the parameter is switched off, then a
switch-off command will also switch the actuator
on. Only visible if a run-on time was set.
Switch off switch-
on delay,
output 2
On, Off
Basic setting: On
With 2-channel inserts, this allows you to switch
off the switch-on delay of output 2. If this is
switched off, output 2 is simultaneously switched
on with output 1.
22 / 29
32597903
07.08.2019
J0082597903