LB management
eNet radio centre plate
Parameters
Setting options, Basic
setting
Explanations
Allow extension
unit operation
On, Off
Basic setting: On
Allows operation via wired extensions.
Extended channel settings Sensor channel
Parameters
Setting options, Basic
setting
Explanations
Manual commis-
sioning
On, Off
Basic setting: On
Blocks manual commissioning for the sensor
channel. In the "Off" setting, the device cannot be
reset to the factory setting.
Local Operation
On, Off
Basic setting: On
Blocks the sensor operation of the button. Tele-
grams are no longer transmitted to remote actu-
ators.
Channel settings "switching"
Parameters
Setting options, Basic
setting
Explanations
Switch-on delay
0 s … 24 h
Basic setting: 0 s
The load switches on after a delay. Repeated
switch-on commands restart the delay time. If the
load has not yet been switched on due to the
delay when a switch-off command comes, then
the load will remain off. In Flashing operating
mode, the pause time is set using this parameter.
Switch-off delay
0 s … 24 h
Basic setting: 0 s
The load switches off after a delay. Repeated
switch-off commands restart the delay time. If the
load has not yet been switched off due to the
delay when a switch-on command comes, then
the load will remain on. In Flashing operating
mode, the pulse times are set using this para-
meter.
Run-on time
0 s … 24 h
Basic setting: 0 s
If a run-on time is entered and the "Use run-on
time" parameter is activated, the actuator no
longer remains permanently switched on, but
only for the duration of the run-on time entered
here or transmitted by a motion detector. The
run-on time is restarted if actuation is repeated.
A motion detector command without transmitted
run-on time (e.g. from an extension) leads to
switching on for the duration of the run-on time
entered here. If no run-on time is entered here,
the default run-on time of 2 minutes is applied.
Use run-on time
On, Off
Basic setting: Off
On:
If a run-on time is configured (≠ 0 s), in addition
to motion detector commands, all switching or
dimming commands also lead to switching on for
the duration of the run-on time.
If no run-on time is configured (= 0 s), all switch-
ing or dimming commands result in permanent
switching of the load.
As soon as the attachment receives a motion de-
tector command, the transmitted run-on time is
11 / 29