LB management
eNet radio centre plate
Parameters
Setting options, Basic
setting
Explanations
The Reset button is used to reset the counter to
"0". The device must be programmed to apply the
change.
Operating hours,
Down
0...65535
Basic setting: Current
value
The time is counted during which the load is
switched on (relay contact closed). This para-
meter can be reset to "0", for example after ex-
changing the load.
The Reset button is used to reset the counter to
"0". The device must be programmed to apply the
change.
Extended channel settings "Venetian blind"
Parameters
Setting options, Basic
setting
Explanations
Operating mode
Roller shutter
Venetian blind
Awning
Basic setting: Roller
shutter
See Device and channels.
Manual commis-
sioning
On, Off
Basic setting: On
Blocks manual commissioning for the device
channel. In the "Off" setting, the device cannot be
reset to the factory setting.
Local Operation
On, Off
Basic setting: On
Blocks the output for operation using the button.
Running time
1 ... 600 sec
Basic setting: 120 s
Absolute time which the blind/shutter requires
from the top to the bottom end position. The entry
is essential if scene or position movements are to
occur.
Slat change-over
time/fabric-
stretching time
0 ms ... 10 sec
300 ms … 10 s
Basic setting: 0 ms / 300
ms
Absolute time for changing-over Venetian blind
slats. The fabric stretching time can also be set
here for the Awning operating mode.
Minimum
change-over-time
300 ms ... 10 sec
Basic setting: 1 s
Minimum interruption time when changing direc-
tions. Increasing the minimum change-over time
will cause less wear on the motors.
Invert movement
direction
On, Off
Basic setting: Off
Inverts the activation of the relay outputs. During
inverted operation, the relay outputs "Up" and
"Down" should be activated in reverse. This is re-
quired, for example, for controlling skylights.
Behaviour on
voltage return
No change
Configured value
Basic setting: No
change
Defines the behaviour of the output after voltage
return. RMD design: Bus voltage return.
Configured vene-
tian blind position
0 ... 100 %
Basic setting: 0 %
If the "Configured position" value is entered for
the parameter "Behaviour after voltage return",
then the blind/shutter position set here is ap-
proached.
Configured slat
position
0 ... 100 % basic setting:
0 %
If the "Configured position" value is entered for
the parameter "Behaviour after voltage return",
then the slat position set here is approached.