6 Functions
22
6.4
Fault signaling
IO-Link offers a range of fault signaling options (device status, event codes, PDValid-Flag). Furthermore,
malfunctions can also be signaled within the process data via the process value itself or the status of the
process value.
Overview
Description
Signaling
via pro-
cess value
in PDI
a
a
PDI = Process Data Input
Process value
status in PDI
(1 byte)
Device status Event code
(Standard
event)
Event
activa-
tion or
deacti-
cation
possi-
ble
Event er-
ror type
No error
-
-
0 (device is
working prop-
erly)
-
-
-
Process value
invalid
Yes
Bit0
(Process data
invalid)
4 (failure)
0x1000
Yes
Error
Overrange
Yes
0x8C20
Yes
Error
Underrange
Yes
Yes
Error
Error in config-
uration data
No
Bit1
(Parameter er-
ror)
4 (failure)
0x6320
No
Error
Error in cali-
bration data
No
Bit2
(Device is de-
fective)
4 (failure)
0x5000
Yes
Error
Device is de-
fective (Probe
break, probe
short circuit)
Yes
Undervoltage
No
-
2 (Outside the
specification)
0x5111
No
Warning
Temperature
error, overload
No
-
4 (failure)
0x4000
No
Error
Summary of Contents for 00725428