15
6 Functions
6
Functions
CAUTION!
Write operations to some R/W parameters result in them being saved to the EEPROM. This mem-
ory module has only a limited number of write cycles (approx. 100,000).
Frequent writing of certain parameters can therefore result in a memory error.
Fast writing cycles should thus be avoided.
6.1
Switching points
Depending on the operating mode, the sensor has 1 or 2 switching outputs. It automatically detects the
connection type and responds accordingly. Separate parameters are available for both switching out-
puts.
Parameter
Operating mode
Output
Pin at the M12 connection
SIO mode
(SIO = Standard IO)
Switching output 1
C/Q (OUT1)
Switching output 2
I/Q (OUT2)
IO-Link mode
IO-Link communication
C/Q (IO-Link)
Switching output 2
I/Q (OUT2)
Parameter
Selection/settings
Description
Switching behavior
Inactive
When inactive is selected, the
selected switching output is not
activated.
Hysteresis function, N/O Contact
Hysteresis function, N/C Contact
Window function, N/O Contact
Window function, N/C Contact
Switching point (SP) or
window high (FH)
-999 to
0
to +999
The selected switching output is
only activated if rSP < SP or
FL < FH.
Chapter 6.1.1
Chapter 6.1.2
Release point (rSP) or
window low (FL)
-999 to
0
to +999
Switch-on delay (VSP)
0
to 100 s
Chapter 6.1.3
Switch-off delay (VrSP)
0
to 100 s
Output driver mode
p-switching
Chapter 4.1
n-switching