12
4 Electrical connection
4
Electrical connection
Connection
Terminal assignment
Switch operation
Voltage supply
a
DC 9.6 to 32 V
1 BN (brown)
b
3 BU (blue)
L+
L-
Switching output 1
4 BK (black)
C/Q = OUT1
Switching output 2
2 WH (white)
I/Q = OUT2
IO-Link operation
Voltage supply
DC 18 to 32 V
1 BN (brown)
3 BU (blue)
L+
L-
IO-Link
4 BK (black)
C/Q = IO-Link
Switching output 2
2 WH (white)
I/Q = OUT2
a
The auxiliary energy of the transmitter must meet SELV requirements. Optionally, an energy-limited electrical circuit
according to DIN EN 61010-1 can be used.
b
The color coding is
only
valid for A-coded standard cables!
BU
BK
WH
BN
L–
C/Q
(
OUT
1)
IO-Link/
I/Q
(
OUT
2)
L+
1
3
4
2