Operating instructions
Installation
39
Run the cable (orange) from the level
sensor (2) of the Salisol tank (1) through the
Salisol level connection (3) on the control
cabinet (4), and fix the cable in position.
Plug in coupler (2) of cable (3) into the level
sensor (1) of the Salisol tank and fasten the
terminal to screw (4).
Fasten the white wire from the Salisol level
sensor cable in the DC INPUT 7 connection
of the PLC.
Fasten the brown wire from the Salisol
level sensor cable to the +24 V terminal (6).
Fasten the blue wire from the Salisol level
sensor cable to the +0 V terminal (5).
Cut off and insulate the black wire from the
Salisol level sensor cable.