Thermalstore
6
A thermostatic mixer should be installed in the system to prevent the risk of scalding.
If there are leaks found in the system, shut off the cold water stop valve from the main
supply and contact a competent person immediately.
WHAT IS BENCHMARK?
Benchmark places responsibilities on both manufacturers and installers. The purpose
is to ensure that customers are provided with the correct equipment for their needs,
that it is installed, commissioned and serviced in accordance with the manufacturer’s
instructions by competent persons and that it meets the requirements of the appro-
priate Building Regulations.
The Benchmark Checklist can be used to demonstrate compliance with Building Reg-
ulations and should be provided to the customer for future reference. Installers are
required to carry out installation, commissioning and servicing work in accordance
with the Benchmark Code of Practice which is available from the Heating and Hotwa-
ter Industry Council who manage and promote the scheme. Visit www.centralheating.
co.uk
WATER SUPPLY
The performance of any unvented system is only as good as the mains water supply
available. To this eff ect the maximum possible water demand should be assessed,
with the knowledge that the mains supplies both hot and cold services
simultaneously.
The water heater itself operates at a pressure of 3 bar, controlled by the inlet control
set, and is capable of delivering over 50 litres per minute. The high quality inlet con-
trol set has been designed to make the most of the fl ow rates available.
The water supply should be checked to ensure it can meet these requirements. If
necessary, consult the local water authority regarding the likely pressure and fl ow rate
availability.
Consideration should be given to upgrading existing ½” (15mm) cold mains pipe-
work to a larger size if the recommended minimum pressure/fl ow rate is not being
achieved. JOULE recommend that primary pipework used has a minimum diameter of
22mm to ensure low pressure loss.
Note: A high static (no fl ow) mains pressure is no guarantee of good fl ow availability.
In a domestic installation 1.5 bar and 25 l/min. should be regarded as the minimum.
The maximum mains pressure that the inlet control set can cope with is 10 bar.
Summary of Contents for Thermalstore 1.0
Page 1: ...1 Thermalstore 1 0 2 0 Installation Manual...
Page 16: ...Thermalstore 16 Thermalstore 1 0 No Solar...
Page 18: ...Thermalstore 18 Thermalstore 1 0 Solar...
Page 20: ...Thermalstore 20 Thermalstore 2 0 No Solar...
Page 22: ...Thermalstore 22 Thermalstore 2 0 Solar...
Page 25: ...25 Electrical Diagram...
Page 27: ...27 Electrical Diagram...
Page 29: ...29 Electrical Diagram...
Page 30: ...Thermalstore 30 Thermalstore Sealed Boiler 2 Radiator Zones Solar Mechanical Diagram...
Page 31: ...31 Electrical Diagram...
Page 32: ...Thermalstore 32 Thermalstore Open Vent Boiler 1 Radiator Zones Mechanical Diagram...
Page 33: ...33 Electrical Diagram...
Page 34: ...Thermalstore 34 Thermalstore Open Vent Boiler 2 Radiator Zones Mechanical Diagram...
Page 35: ...35 Electrical Diagram...
Page 36: ...Thermalstore 36 Thermalstore Solid Fuel Boiler 2 Radiator Zones Mechanical Diagram...
Page 37: ...37 Electrical Diagram...
Page 38: ...Thermalstore 38 Thermalstore Solid Fuel Boiler 2 Radiator Zones Mechanical Diagram...
Page 39: ...39 Electrical Diagram...
Page 41: ...41 Electrical Diagram Electrical Diagram...
Page 43: ...43 Electrical Diagram...
Page 45: ...45 Electrical Diagram...
Page 47: ...47 Electrical Diagram...
Page 64: ...Thermalstore 64 Mains Pressure Hot...
Page 65: ...65 Water Storage System Commisioning Checklist...
Page 66: ...Thermalstore 66...
Page 67: ...67 Service Record...