55
Check the pressure in the expansion vessel is charged to 3 bar
. Turn off the water
supply to the unit and open a hot tap first. The air valve on expansion vessel is a
Schrader (car tyre) type.
Air or CO2 may be used to charge the expansion vessel. Unscrew the head on the
inlet control set and clean the mesh fi lter within. The Service Log Book supplied
with this unit should be updated at each service.
YOUR GUARANTEE MAY BE VOID IF YOU CANNOT PRODUCE PROOF OF ANNUAL
SERVICING
IMMERSION HEATER REPLACEMENT
If the thermal cut out on the Immersion heater operates contact a competent
installer. If the thermal cut out fault occurs again the immersion will need to be
replaced. Prior to installing the replacement Immersion, ensure the o-ring is correct-
ly positioned on the head of the Immersion and lubricate the threads before fi tting.
Thread the Immersion by hand until it is hand tight and then tighten gently to allow
the o-rings to create a water tight seal.
INSPECTION
Where internal inspection of the cylinder is required an endoscope can be used.
Inspection can be carried out by draining down the cylinder and removing a
component that is fi tted to a wet connection in the cylinder.
SAFETY VALVE CHECKS
Any sign of water coming from either the temperature/pressure relief valve or the
expansion relief valve indicates a problem.
Check your discharge pipework is free from debris and is carrying water away to
waste eff ectively. Next hold both of these safety valves open, allowing as much
water as possible to fl ow through the tundish. Release the valves and check that
they reseat correctly.
Completion of the Benchmark checklist on pages
32 – 33
MUST be adhered to by
the installer.
Summary of Contents for Thermalstore 1.0
Page 1: ...1 Thermalstore 1 0 2 0 Installation Manual...
Page 16: ...Thermalstore 16 Thermalstore 1 0 No Solar...
Page 18: ...Thermalstore 18 Thermalstore 1 0 Solar...
Page 20: ...Thermalstore 20 Thermalstore 2 0 No Solar...
Page 22: ...Thermalstore 22 Thermalstore 2 0 Solar...
Page 25: ...25 Electrical Diagram...
Page 27: ...27 Electrical Diagram...
Page 29: ...29 Electrical Diagram...
Page 30: ...Thermalstore 30 Thermalstore Sealed Boiler 2 Radiator Zones Solar Mechanical Diagram...
Page 31: ...31 Electrical Diagram...
Page 32: ...Thermalstore 32 Thermalstore Open Vent Boiler 1 Radiator Zones Mechanical Diagram...
Page 33: ...33 Electrical Diagram...
Page 34: ...Thermalstore 34 Thermalstore Open Vent Boiler 2 Radiator Zones Mechanical Diagram...
Page 35: ...35 Electrical Diagram...
Page 36: ...Thermalstore 36 Thermalstore Solid Fuel Boiler 2 Radiator Zones Mechanical Diagram...
Page 37: ...37 Electrical Diagram...
Page 38: ...Thermalstore 38 Thermalstore Solid Fuel Boiler 2 Radiator Zones Mechanical Diagram...
Page 39: ...39 Electrical Diagram...
Page 41: ...41 Electrical Diagram Electrical Diagram...
Page 43: ...43 Electrical Diagram...
Page 45: ...45 Electrical Diagram...
Page 47: ...47 Electrical Diagram...
Page 64: ...Thermalstore 64 Mains Pressure Hot...
Page 65: ...65 Water Storage System Commisioning Checklist...
Page 66: ...Thermalstore 66...
Page 67: ...67 Service Record...