9
SITING THE UNIT
This unit can supply outlets above it or at some distance from it but any outlets
above the unit will reduce the available outlet pressure by 0.1 bar for every 1m of
height diff erence. The maximum length of the “dead leg” should be as stated in the
Water Supply (Water Fittings) Regulations 1999 G18.7, in particular to the area of
most frequent use.
Particular attention is needed if sitting in a garage or outbuilding as the unit should
be protected from frost. All exposed pipework must be insulated. The unit must be
installed
UPRIGHT
on a fl at base capable of supporting its weight when full (please
see the technical specification section for weights).
Suffi
cient access to allow maintenance of the valves should be considered. In
addition the immersion heaters are 400mm in length and this distance should be
considered to allow withdrawal for servicing if required. The discharge pipework
from the safety valves should fall continuously and terminate safely.
COLD MAINS PIPEWORK
Run the cold main through the building to the place where is to be installed. Take
care not to run the cold pipe near hot water or heating pipe work so that the heat
pick-up is minimized. Identify the cold water supply pipe and fi t an isolating valve
(not supplied). A 22mm BS1010 stopcock can typically be used but a 22mm quarter
turn full bore valve would be better as it does not restr
ict the fl ow as much. Do not
use “screwdriver slot” or similar valves.
Make the connection to the cold feed of the DHW coil cylinder and incorporate a
drain valve. Ensure that the arrow points in the direction of the water fl ow. Select
a suitable position for the expansion vessel. Mount it to the wall using the bracket
provided. Use the fl exible hose provided to connect to the inlet control group.
BALANCED COLD CONNECTION
If there are to be showers, bidets or monobloc taps in the installation then a bal-
anced cold supply is necessary. There is a 22mm balanced connection on the inlet
control set.
General Requirements
Summary of Contents for Thermalstore 1.0
Page 1: ...1 Thermalstore 1 0 2 0 Installation Manual...
Page 16: ...Thermalstore 16 Thermalstore 1 0 No Solar...
Page 18: ...Thermalstore 18 Thermalstore 1 0 Solar...
Page 20: ...Thermalstore 20 Thermalstore 2 0 No Solar...
Page 22: ...Thermalstore 22 Thermalstore 2 0 Solar...
Page 25: ...25 Electrical Diagram...
Page 27: ...27 Electrical Diagram...
Page 29: ...29 Electrical Diagram...
Page 30: ...Thermalstore 30 Thermalstore Sealed Boiler 2 Radiator Zones Solar Mechanical Diagram...
Page 31: ...31 Electrical Diagram...
Page 32: ...Thermalstore 32 Thermalstore Open Vent Boiler 1 Radiator Zones Mechanical Diagram...
Page 33: ...33 Electrical Diagram...
Page 34: ...Thermalstore 34 Thermalstore Open Vent Boiler 2 Radiator Zones Mechanical Diagram...
Page 35: ...35 Electrical Diagram...
Page 36: ...Thermalstore 36 Thermalstore Solid Fuel Boiler 2 Radiator Zones Mechanical Diagram...
Page 37: ...37 Electrical Diagram...
Page 38: ...Thermalstore 38 Thermalstore Solid Fuel Boiler 2 Radiator Zones Mechanical Diagram...
Page 39: ...39 Electrical Diagram...
Page 41: ...41 Electrical Diagram Electrical Diagram...
Page 43: ...43 Electrical Diagram...
Page 45: ...45 Electrical Diagram...
Page 47: ...47 Electrical Diagram...
Page 64: ...Thermalstore 64 Mains Pressure Hot...
Page 65: ...65 Water Storage System Commisioning Checklist...
Page 66: ...Thermalstore 66...
Page 67: ...67 Service Record...